Heat of extraction/rejection data, Envision, Compact - 50 hz installation manual – WaterFurnace Envision2 User Manual
Page 47
47
ENVISION
2
COMPACT - 50 HZ INSTALLATION MANUAL
Heat of Extraction/Rejection Data
Model
L/s
Heat of Extraction (kW)
Heat of Rejection (kW)
-1.11°C
10°C
21.1°C
32.2°C
-1.11°C
10°C
21.1°C
32.2°C
43.3°C
005
Full Load
0.19
3.34
4.07
5.60
6.74
6.33
6.0
0.25
2.96
3.58
4.34
5.71
6.2
6.83
6.36
6.0
5.9
0.32
3.05
3.84
4.63
5.80
6.2
6.92
6.42
6.1
5.9
006
Part Load
0.19
4.10
5.51
6.68
7.82
7.80
7.1
0.32
2.99
4.34
5.80
7.03
7.2
7.85
7.82
7.1
6.5
0.44
3.02
4.43
5.89
7.15
7.3
7.91
7.82
7.1
6.5
Full Load
0.25
5.45
7.12
8.67
10.20
10.23
9.8
0.38
4.10
5.77
7.53
9.11
9.8
10.23
10.26
9.8
9.1
0.50
4.19
5.89
7.65
9.29
9.9
10.29
10.29
9.8
9.1
009
Part Load
0.25
5.16
6.68
8.06
10.35
10.11
9.5
0.38
3.69
5.36
7.03
8.56
9.5
10.43
10.17
9.5
8.9
0.50
3.99
5.66
7.21
8.56
9.7
10.58
10.32
9.6
9.0
Full Load
0.32
7.36
9.20
10.52
14.16
14.21
13.4
0.44
5.51
7.68
9.70
11.25
13.2
14.30
14.42
13.7
12.8
0.57
5.63
7.88
9.99
11.63
13.3
14.39
14.54
13.8
12.8
012
Part Load
0.32
6.80
8.38
9.58
13.89
14.21
13.5
0.50
5.39
7.50
9.29
10.70
12.6
13.92
14.16
13.4
12.4
0.69
5.60
7.80
9.79
11.40
12.4
13.92
14.27
13.6
12.7
Full Load
0.38
9.82
11.96
13.54
18.58
18.52
17.3
0.57
7.65
10.20
12.60
14.45
17.3
18.61
18.73
17.6
16.1
0.76
7.82
10.49
13.01
14.98
17.4
18.67
18.84
17.7
16.2
015
Part Load
0.38
9.55
12.02
14.07
17.76
17.41
16.3
0.63
6.68
9.64
12.51
15.18
16.6
17.73
17.44
16.4
15.3
0.88
7.00
9.99
12.78
15.21
16.5
17.73
17.47
16.4
15.4
Full Load
0.50
12.87
16.53
20.22
23.74
24.30
22.4
0.76
10.1
13.77
17.26
20.57
21.6
23.89
24.44
22.5
20.9
1.01
10.2
14.04
17.79
21.42
21.7
24.03
24.56
22.6
21.0
017
Full Load
0.76
15.36
19.61
22.89
26.70
26.23
24.3
0.95
11.1
15.74
20.46
24.30
24.4
26.73
26.20
24.2
22.5
1.14
11.2
15.91
20.78
24.85
24.6
26.93
26.46
24.5
22.7
6/25/12