COMPACT - 50 HZ INSTALLATION MANUAL

Load Shed

The LS input disables all outputs with the exception of

the blower output. When the LS input has been cleared,

the anti-short cycle timer and random start timer will be

initiated. Input must be tied to common to activate.

LED Displays

These three LEDs display the status, configuration, and

fault codes for the control. These can also be read in plain

English via the Aurora AID Tool.

Status LED (LED3, Green)

Description of Operation

Fault LED, Green

Normal Mode

ON

Control is Non-functional

OFF

Test Mode

Slow Flash

Lockout Active

Fast Flash

Dehumidification Mode

Flash Code 2

(Reserved)

Flash Code 3

(Reserved)

Flash Code 4

Load Shed

Flash Code 5

ESD

Flash Code 6

(Reserved)

Flash Code 7

Configuration LED (LED2, Yellow)

Description of Operation

Configuration LED, Yellow

No Software Overwritten

Flashing Variable Speed ECM

Setting

DIP Switch was Overwritten

Slow Flash

Variable Speed ECM
Configuration Mode

Fast Flash

Fault LED (LED1, Red)

Description of Operation

Fault LED, Red

Normal Mode

OFF

Input Fault Lockout

Flash Code 1

High Pressure Lockout

Flash Code 2

Low Pressure Lockout

Flash Code 3

Freeze Detection 2 - (Future Use)

Flash Code 4

Freeze Detection 1 - (Coax)

Flash Code 5

(Reserved)

Flash Code 6

Condensate Overflow

Flash Code 7

Over/Under Voltage Shutdown

Flash Code 8

Freeze Detection Sensor Error
(Sensor is Out of Range)

Flash Code 11

Aurora Interface and Design (AID) Tool

The Aurora Interface and

Diagnostics (AID) Tool is

a device that is a member

of the Aurora network.

The AID Tool is used to

troubleshoot equipment

which uses the Aurora

control via Modbus RTU

communication. The AID

Tool provides diagnostics,

fault management, variable speed ECM setup, and system

configuration capabilities to the Aurora family of controls.

An AID Tool is recommended, although not required, for

variable speed ECM airflow settings.

ABC Control Board Layout

1

CC2

EH1

Factory

Fault

ALG

ALM

LS

ES

ACC c

Status

AURORA BASE

CONTROL™

RV – K1

CC2

CC – K2

CC Hi – K3

Fan – K4

Alarm – K5

Acc – K6

ACC no

ACC nc

O/B

C

R

LO

G

Y1

Y2

W

DH

3A-Fuse

O/B

C

R

LO

G

Y1

Y2

W

DH

LO

G

HI

CCG

CC
FG

F
R

HP
HP

LP

FP2
FP2
FP1

REV
REV

CFM

PWM

ECM PWM

Factory

Factory Fan Connection

R

R

CC

C

C

R

(-)

(+)

RS 485

EH2

C

EH1

C

CO

(+)

(-)

R
C

RS485 Exp

Factory

Com1

Com2

Config

G

G

G

Y

R

SW1 Test

FP1 – 15

o

F/30

o

F

JW2 -
Alarm

P11

P5

P2

P1

P8

P7

P9

P6

P3

SW2

P13

P4

FP2 – 15

o

F/30

o

F

RV – B/O

ACC – Dip 4

ACC – Dip 5

CC – Dual/Single

L – Pulse/Continuous

Reheat/Normal

Factory Use

Field Connections

Field Connections

C

LP

FP1

F

CC

G

Y1

1

2

3

4

5

6

7

8

Off

On

N/A

RS485 NET

LED3

LED2

LED1

Controls - Aurora Base Control cont.