Controls - aurora base control cont, Led displays, Aurora interface and design (aid) tool – WaterFurnace Envision2 User Manual
Page 31: Abc control board layout, Envision, Compact - 50 hz installation manual, Status led (led3, green), Configuration led (led2, yellow), Fault led (led1, red), Aurora base control
31
ENVISION
2
COMPACT - 50 HZ INSTALLATION MANUAL
Load Shed
The LS input disables all outputs with the exception of
the blower output. When the LS input has been cleared,
the anti-short cycle timer and random start timer will be
initiated. Input must be tied to common to activate.
LED Displays
These three LEDs display the status, configuration, and
fault codes for the control. These can also be read in plain
English via the Aurora AID Tool.
Status LED (LED3, Green)
Description of Operation
Fault LED, Green
Normal Mode
ON
Control is Non-functional
OFF
Test Mode
Slow Flash
Lockout Active
Fast Flash
Dehumidification Mode
Flash Code 2
(Reserved)
Flash Code 3
(Reserved)
Flash Code 4
Load Shed
Flash Code 5
ESD
Flash Code 6
(Reserved)
Flash Code 7
Configuration LED (LED2, Yellow)
Description of Operation
Configuration LED, Yellow
No Software Overwritten
Flashing Variable Speed ECM
Setting
DIP Switch was Overwritten
Slow Flash
Variable Speed ECM
Configuration Mode
Fast Flash
Fault LED (LED1, Red)
Description of Operation
Fault LED, Red
Normal Mode
OFF
Input Fault Lockout
Flash Code 1
High Pressure Lockout
Flash Code 2
Low Pressure Lockout
Flash Code 3
Freeze Detection 2 - (Future Use)
Flash Code 4
Freeze Detection 1 - (Coax)
Flash Code 5
(Reserved)
Flash Code 6
Condensate Overflow
Flash Code 7
Over/Under Voltage Shutdown
Flash Code 8
Freeze Detection Sensor Error
(Sensor is Out of Range)
Flash Code 11
Aurora Interface and Design (AID) Tool
The Aurora Interface and
Diagnostics (AID) Tool is
a device that is a member
of the Aurora network.
The AID Tool is used to
troubleshoot equipment
which uses the Aurora
control via Modbus RTU
communication. The AID
Tool provides diagnostics,
fault management, variable speed ECM setup, and system
configuration capabilities to the Aurora family of controls.
An AID Tool is recommended, although not required, for
variable speed ECM airflow settings.
ABC Control Board Layout
1
CC2
EH1
Factory
Fault
ALG
ALM
LS
ES
ACC c
Status
AURORA BASE
CONTROL™
RV – K1
CC2
CC – K2
CC Hi – K3
Fan – K4
Alarm – K5
Acc – K6
ACC no
ACC nc
O/B
C
R
LO
G
Y1
Y2
W
DH
3A-Fuse
O/B
C
R
LO
G
Y1
Y2
W
DH
LO
G
HI
CCG
CC
FG
F
R
HP
HP
LP
FP2
FP2
FP1
REV
REV
CFM
PWM
ECM PWM
Factory
Factory Fan Connection
R
R
CC
C
C
R
(-)
(+)
RS 485
EH2
C
EH1
C
CO
(+)
(-)
R
C
RS485 Exp
Factory
Com1
Com2
Config
G
G
G
Y
R
SW1 Test
FP1 – 15
o
F/30
o
F
JW2 -
Alarm
P11
P5
P2
P1
P8
P7
P9
P6
P3
SW2
P13
P4
FP2 – 15
o
F/30
o
F
RV – B/O
ACC – Dip 4
ACC – Dip 5
CC – Dual/Single
L – Pulse/Continuous
Reheat/Normal
Factory Use
Field Connections
Field Connections
C
LP
FP1
F
CC
G
Y1
1
2
3
4
5
6
7
8
Off
On
N/A
RS485 NET
LED3
LED2
LED1
Controls - Aurora Base Control cont.