Refrigerant circuit guideline, Compressor resistance, Thermistor resistance – WaterFurnace Envision2 User Manual

Page 46: Envision, Compact - 50 hz installation manual

background image

46

ENVISION

2

COMPACT - 50 HZ INSTALLATION MANUAL

Compressor Resistance

Thermistor

Temperature (°C)

Microprocessor

Resistance (Ohms)

FX10

Resistance (Ohms)

-15

75757-70117

746-770

-10

57392-53234

775-803

-5

43865-40771

808-836

0

33809-31487

841-869

5

26269-24513

875-903

10

20570-19230

910-938

15

16226-15196

946-974

20

12889-12093

981-1013

25

10310-9688

1019-1051

30

8300-7812

1058-1090

35

6723-6337

1097-1129

40

5480-5172

1137-1169

45

4490-4246

1179-1211

50

3700-3504

1221-1253

55

3067-2907

1261-1297

60

2554-2424

1305-1341

65

2149-2019

1350-1386

6/25/12

Thermistor Resistance

Model

220-240/50/1

460/60/3

Run

Start

Single

Speed

005

3.03 - 3.49

2.39 - 2.75

n/a

017

0.37-0.43

1.09-1.25

2.34 - 2.70

Dual

Capacity

006

1.38 - 1.58

2.02 - 2.32

8.00 - 9.20

009

1.13 - 1.31

1.07 - 1.23

5.46 - 6.28

012

0.65-0.75

0.82-0.94

3.88 - 4.46

015

0.48-0.56

0.81-0.93

2.98 - 3.42

6/25/12

Symptom

Head

Pressure

Suction

Pressure

Compressor

Amp Draw

Superheat

Subcooling

Air Temp.

Differential

Water Temp.

Differential

Under Charged System (Possible Leak)

Low

Low

Low

High

Low

Low

Low

Over Charged System

High

High

High

Normal

High

Normal/Low

Normal

Low Air Flow Heating

High

High

High

High/Normal

Low

High

Low

Low Air Flow Cooling

Low

Low

Low

Low/Normal

High

High

Low

Low Water Flow Heating

Low/Normal

Low/Normal

Low

Low

High

Low

High

Low Water Flow Cooling

High

High

High

High

Low

Low

High

High Air Flow Heating

Low

Low

Low

Low

High

Low

Low

High Air Flow Cooling

Low

High

Normal

High

Low

Low

Normal

High Water Flow Heating

Normal

Low

Normal

High

Normal

Normal

Low

High Water Flow Cooling

Low

Low

Low

Low

High

Normal

Low

Low Indoor Air Temperature Heating

Low

Low

Low

Normal

High

Normal

Normal/High

Low Indoor Air Temperature Cooling

Low

Low

Low

Normal/Low

High

Low

Low

High Indoor Air Temperature Heating

High

High

High

Normal/High

Normal/Low

Low

Normal

High Indoor Air Temperature Cooling

High

High

High

High

Low

Low

High

Restricted TXV (Check Service Advisory)

High

Low

Normal/Low

High

High

Low

Low

Insufficient Compressor (Possible Bad Valves)

Low

High

Low

High

Normal/High

Low

Low

TXV - Bulb Loss of Charge

Low

Low

Low

High

High

Low

Low

Scaled Coaxial Heat Exchanger Heating

Low

Low

Low

Normal/Low

High

Low

Low

Scaled Coaxial Heat Exchanger Cooling

High

High

High

Normal/Low

Low

Low

Low

Restricted Filter Drier

Check temperature difference (delta T) across filter drier.

7/6/10

Refrigerant Circuit Guideline