Refrigerant circuit guideline, Compressor resistance, Thermistor resistance – WaterFurnace Envision2 User Manual
Page 46: Envision, Compact - 50 hz installation manual
46
ENVISION
2
COMPACT - 50 HZ INSTALLATION MANUAL
Compressor Resistance
Thermistor
Temperature (°C)
Microprocessor
Resistance (Ohms)
FX10
Resistance (Ohms)
-15
75757-70117
746-770
-10
57392-53234
775-803
-5
43865-40771
808-836
0
33809-31487
841-869
5
26269-24513
875-903
10
20570-19230
910-938
15
16226-15196
946-974
20
12889-12093
981-1013
25
10310-9688
1019-1051
30
8300-7812
1058-1090
35
6723-6337
1097-1129
40
5480-5172
1137-1169
45
4490-4246
1179-1211
50
3700-3504
1221-1253
55
3067-2907
1261-1297
60
2554-2424
1305-1341
65
2149-2019
1350-1386
6/25/12
Thermistor Resistance
Model
220-240/50/1
460/60/3
Run
Start
Single
Speed
005
3.03 - 3.49
2.39 - 2.75
n/a
017
0.37-0.43
1.09-1.25
2.34 - 2.70
Dual
Capacity
006
1.38 - 1.58
2.02 - 2.32
8.00 - 9.20
009
1.13 - 1.31
1.07 - 1.23
5.46 - 6.28
012
0.65-0.75
0.82-0.94
3.88 - 4.46
015
0.48-0.56
0.81-0.93
2.98 - 3.42
6/25/12
Symptom
Head
Pressure
Suction
Pressure
Compressor
Amp Draw
Superheat
Subcooling
Air Temp.
Differential
Water Temp.
Differential
Under Charged System (Possible Leak)
Low
Low
Low
High
Low
Low
Low
Over Charged System
High
High
High
Normal
High
Normal/Low
Normal
Low Air Flow Heating
High
High
High
High/Normal
Low
High
Low
Low Air Flow Cooling
Low
Low
Low
Low/Normal
High
High
Low
Low Water Flow Heating
Low/Normal
Low/Normal
Low
Low
High
Low
High
Low Water Flow Cooling
High
High
High
High
Low
Low
High
High Air Flow Heating
Low
Low
Low
Low
High
Low
Low
High Air Flow Cooling
Low
High
Normal
High
Low
Low
Normal
High Water Flow Heating
Normal
Low
Normal
High
Normal
Normal
Low
High Water Flow Cooling
Low
Low
Low
Low
High
Normal
Low
Low Indoor Air Temperature Heating
Low
Low
Low
Normal
High
Normal
Normal/High
Low Indoor Air Temperature Cooling
Low
Low
Low
Normal/Low
High
Low
Low
High Indoor Air Temperature Heating
High
High
High
Normal/High
Normal/Low
Low
Normal
High Indoor Air Temperature Cooling
High
High
High
High
Low
Low
High
Restricted TXV (Check Service Advisory)
High
Low
Normal/Low
High
High
Low
Low
Insufficient Compressor (Possible Bad Valves)
Low
High
Low
High
Normal/High
Low
Low
TXV - Bulb Loss of Charge
Low
Low
Low
High
High
Low
Low
Scaled Coaxial Heat Exchanger Heating
Low
Low
Low
Normal/Low
High
Low
Low
Scaled Coaxial Heat Exchanger Cooling
High
High
High
Normal/Low
Low
Low
Low
Restricted Filter Drier
Check temperature difference (delta T) across filter drier.
7/6/10
Refrigerant Circuit Guideline