Operating limits, Operating parameters, Single speed models – WaterFurnace Envision2 User Manual
Page 42: Envision, Compact - 50 hz installation manual
42
ENVISION
2
COMPACT - 50 HZ INSTALLATION MANUAL
Operating Parameters
Single Speed Models
Entering Water
Temp °C
Water Flow
L/s per kW
Cooling -- No Hot Water Generation
Suction Pressure
kPa
Discharge
Pressure kPa
Superheat
Subcooling
Water Temp Rise
°C
Air Temp Drop
°C DB
-1.1
0.09
793 - 862
1034 - 1172
11 - 19
6 - 9
9 - 12
9 - 13
0.19
724 - 827
896 - 1000
11 - 19
6 - 9
4 - 6
9 - 13
10
0.09
896 - 965
1482 - 1620
7 - 11
4 - 8
9 - 12
9 - 13
0.19
883 - 951
1310 - 1448
7 - 11
4 - 8
4 - 7
9 - 13
21.1
0.09
951 - 1020
1931 - 2137
6 - 9
6 - 9
8 - 12
9 - 13
0.19
938 - 1007
1724- 1931
6 - 9
4 - 8
4 - 7
9 - 13
32.2
0.09
1000 - 1069
2413 - 2620
5- 8
6 - 9
8 - 11
9 - 13
0.19
986 - 1055
2206 - 2413
5- 8
4 - 8
3 - 6
9 - 13
43.3
0.09
1000 - 1063
2896 - 3102
5- 8
6 - 9
8 - 11
9 - 13
0.19
986 - 1055
2792 - 2999
5- 8
4 - 8
3 - 6
9 - 13
Entering Water
Temp °C
Water Flow
L/s per kW
Heating - No Hot Water Generation
Suction Pressure
kPa
Discharge
Pressure kPa
Superheat
Subcooling
Water Temp Drop
°C
Air Temp Rise
°C DB
-1.1
0.09
503-586
1862- 2103
4 - 8
2 - 6
3 - 6
8 - 12
0.19
531 - 621
1931 - 2172
4 - 8
2 - 6
2 - 4
9 - 13
10
0.09
669 - 758
1999 - 2241
6 - 9
2 - 6
5 - 7
12 - 16
0.19
703 - 793
2068- 2310
6 - 9
2 - 6
4 - 6
13 - 17
21.1
0.09
896- 1000
2206 - 2448
7 - 11
2 - 6
6 - 8
17 - 20
0.19
931 - 1034
2241 - 2482
7 - 11
2 - 6
4 - 7
18 - 21
32.2
0.09
1034 - 1103
2413 - 2689
7 - 11
2 - 6
6 - 8
17 - 20
0.19
1069- 1038
2517 - 2792
7 - 11
2 - 6
4 - 7
18-21
43.3
0.09
0.19
NOTE: Cooling performance based on entering air temperatures of 26.7°C DB, 67°C WB.
Heating performance based on entering air temperature of 21.1°C DB.
6/25/12
Operating Limits
Operating Limits
Cooling (°C)
Heating (°C)
Air Limits
Min. Ambient Air
7.2
7.2
Rated Ambient Air
26.7
21.1
Max. Ambient Air
37.8
29.4
Min. Entering Air
10.0
4.4
Rated Entering Air db/wb
27/19
20.0
Max. Entering Air db/wb
43/28.3
26.7
Water Limits
Min. Entering Water
-1.1
-6.7
Normal Entering Water
10-43.3
-1.1
Max. Entering Water
48.9
32.2
NOTE: Minimum/maximum limits are only for startup conditions, and
are meant for bringing the space up to occupancy temperature. Units
are not designed to operate at the minimum/maximum conditions on
a regular basis. The operating limits are dependent upon three primary
factors: 1) water temperature, 2) return air temperature, and 3) ambient
temperature. When any of the factors are at the minimum or maximum
levels, the other two factors must be at the normal level for proper and
reliable unit operation.