beautypg.com

Operating limits, Operating parameters, Single speed models – WaterFurnace Envision2 User Manual

Page 42: Envision, Compact - 50 hz installation manual

background image

42

ENVISION

2

COMPACT - 50 HZ INSTALLATION MANUAL

Operating Parameters

Single Speed Models

Entering Water

Temp °C

Water Flow

L/s per kW

Cooling -- No Hot Water Generation

Suction Pressure

kPa

Discharge

Pressure kPa

Superheat

Subcooling

Water Temp Rise

°C

Air Temp Drop

°C DB

-1.1

0.09

793 - 862

1034 - 1172

11 - 19

6 - 9

9 - 12

9 - 13

0.19

724 - 827

896 - 1000

11 - 19

6 - 9

4 - 6

9 - 13

10

0.09

896 - 965

1482 - 1620

7 - 11

4 - 8

9 - 12

9 - 13

0.19

883 - 951

1310 - 1448

7 - 11

4 - 8

4 - 7

9 - 13

21.1

0.09

951 - 1020

1931 - 2137

6 - 9

6 - 9

8 - 12

9 - 13

0.19

938 - 1007

1724- 1931

6 - 9

4 - 8

4 - 7

9 - 13

32.2

0.09

1000 - 1069

2413 - 2620

5- 8

6 - 9

8 - 11

9 - 13

0.19

986 - 1055

2206 - 2413

5- 8

4 - 8

3 - 6

9 - 13

43.3

0.09

1000 - 1063

2896 - 3102

5- 8

6 - 9

8 - 11

9 - 13

0.19

986 - 1055

2792 - 2999

5- 8

4 - 8

3 - 6

9 - 13

Entering Water

Temp °C

Water Flow

L/s per kW

Heating - No Hot Water Generation

Suction Pressure

kPa

Discharge

Pressure kPa

Superheat

Subcooling

Water Temp Drop

°C

Air Temp Rise

°C DB

-1.1

0.09

503-586

1862- 2103

4 - 8

2 - 6

3 - 6

8 - 12

0.19

531 - 621

1931 - 2172

4 - 8

2 - 6

2 - 4

9 - 13

10

0.09

669 - 758

1999 - 2241

6 - 9

2 - 6

5 - 7

12 - 16

0.19

703 - 793

2068- 2310

6 - 9

2 - 6

4 - 6

13 - 17

21.1

0.09

896- 1000

2206 - 2448

7 - 11

2 - 6

6 - 8

17 - 20

0.19

931 - 1034

2241 - 2482

7 - 11

2 - 6

4 - 7

18 - 21

32.2

0.09

1034 - 1103

2413 - 2689

7 - 11

2 - 6

6 - 8

17 - 20

0.19

1069- 1038

2517 - 2792

7 - 11

2 - 6

4 - 7

18-21

43.3

0.09

0.19

NOTE: Cooling performance based on entering air temperatures of 26.7°C DB, 67°C WB.

Heating performance based on entering air temperature of 21.1°C DB.

6/25/12

Operating Limits

Operating Limits

Cooling (°C)

Heating (°C)

Air Limits

Min. Ambient Air

7.2

7.2

Rated Ambient Air

26.7

21.1

Max. Ambient Air

37.8

29.4

Min. Entering Air

10.0

4.4

Rated Entering Air db/wb

27/19

20.0

Max. Entering Air db/wb

43/28.3

26.7

Water Limits

Min. Entering Water

-1.1

-6.7

Normal Entering Water

10-43.3

-1.1

Max. Entering Water

48.9

32.2

NOTE: Minimum/maximum limits are only for startup conditions, and
are meant for bringing the space up to occupancy temperature. Units
are not designed to operate at the minimum/maximum conditions on
a regular basis. The operating limits are dependent upon three primary
factors: 1) water temperature, 2) return air temperature, and 3) ambient
temperature. When any of the factors are at the minimum or maximum
levels, the other two factors must be at the normal level for proper and
reliable unit operation.