beautypg.com

Electrical data, Speed motor, Variable speed ecm motor – WaterFurnace Envision2 User Manual

Page 18: Envision, Compact - 50 hz installation manual

background image

18

ENVISION

2

COMPACT - 50 HZ INSTALLATION MANUAL

Electrical Data

5-Speed Motor

Model

Rated

Voltage

Voltage

Min/Max

Compressor

Blower

Motor

FLA

Total

Unit
FLA

Min

Circ

Amp

Max

Fuse/HACR

Breaker

MCC

RLA

LRA

LRA*

Single

Speed

005

220-240/50/1

198/264

13.1

5.5

24.0

9.6

4.1

9.6

11.0

15

017

220-240/50/1

198/264

38.2

24.5

153.0

61.2

7.6

32.1

38.2

60

380-420/50/3

342/462

13.3

8.5

67.1

40.3

4.0

12.5

14.6

20

Dual Capacity

006

220-240/50/1

198/264

14.4

9.2

52.0

20.8

4.1

13.3

15.6

20

380-420/50/3

342/462

5.0

3.2

27.0

16.2

2.1

5.3

6.1

10/15

009

220-240/50/1

198/264

19.3

12.4

67.0

26.8

4.1

16.5

19.6

30

380-420/50/3

342/462

8.0

5.1

38.0

22.8

2.1

7.2

8.5

10/15

012

220-240/50/1

198/264

24.2

15.5

99.6

39.8

7.6

23.1

27.0

40

380-420/50/3

342/462

9.5

6.1

43.0

25.8

4.0

10.1

11.6

15

015

220-240/50/1

198/264

33.6

24.0

126.0

50.4

7.6

31.6

37.6

60

380-420/50/3

342/462

10.8

6.9

51.5

30.9

4.0

10.9

12.6

15

HACR circuit breaker in USA only
*With optional IntelliStart

5/21/13

Variable Speed ECM Motor

Model

Rated

Voltage

Voltage

Min/Max

Compressor

Blower

Motor

FLA

Total

Unit
FLA

Min

Circ

Amp

Max

Fuse/HACR

Breaker

MCC

RLA

LRA

LRA*

Single

Speed

005

220-240/50/1

198/264

13.1

5.5

24.0

9.6

4.0

9.5

10.9

15

017

220-240/50/1

198/264

38.2

24.5

153.0

61.2

7.0

31.5

37.6

60

380-420/50/3

342/462

13.3

8.5

67.1

40.3

6.9

15.4

17.5

25

Dual Capacity

006

220-240/50/1

198/264

14.4

9.2

52.0

20.8

4.0

13.2

15.5

20

380-420/50/3

342/462

5.0

3.2

27.0

16.2

4.1

7.3

8.1

10/15

009

220-240/50/1

198/264

19.3

12.4

67.0

26.8

4.0

16.4

19.5

30

380-420/50/3

342/462

8.0

5.1

38.0

22.8

4.1

9.2

10.5

15

012

220-240/50/1

198/264

24.2

15.5

99.6

39.8

4.0

19.5

23.4

35

380-420/50/3

342/462

9.5

6.1

43.0

25.8

4.1

10.2

11.7

15

015

220-240/50/1

198/264

33.6

24.0

126.0

50.4

7.0

31.0

37.0

60

380-420/50/3

342/462

10.8

6.9

51.5

30.9

6.9

13.8

15.5

20

HACR circuit breaker in USA only
Neutral wire required for variable speed ECM motor on 380-420V application.
*With optional IntelliStart

5/21/13