beautypg.com

Blower performance data, Speed ecm constant torque motors, Speed ecm blower motor – WaterFurnace Envision2 User Manual

Page 19: Setting blower speed - 5-speed ecm, Envision, Compact - 50 hz installation manual

background image

19

ENVISION

2

COMPACT - 50 HZ INSTALLATION MANUAL

5-Speed ECM Constant Torque Motors

The 5-speed ECM is a ‘Constant Torque’ ECM motor and
delivers air flow similar to a PSC but operates as efficiently as
a variable speed ECM motor. Because it is an ECM motor, the
5-speed ECM can ramp slowly up or down like the variable
speed ECM motor. There are 5 possible speed taps available
on the 5-speed ECM motor with #1 being the lowest airflow
and #5 being the highest airflow. These speed selections are
preset at the time of manufacture and are easily changed in
the field if necessary.

If more than one tap are energized at the same time, built
in logic gives precedence to the highest tap number and
allows air flow to change with G, Y1, Y2 and W signals. Each
of those 5 speeds has a specific ‘Torque’ value programmed
into the motor for each speed selection. As static pressure
increases, airflow decreases resulting in less torque on the
rotor. The motor responds only to changes in torque and
adjusts its speed accordingly.

The 5-speed ECM motor is powered by line voltage but the
motor speed is energized by 24VAC.

5-Speed ECM Benefits:

- High efficiency
- Soft start
- 5 speeds with up to 4 speeds on-line
- Built in logic allows air flow to change with G, Y1, Y2

and W signals

- Super efficient low airflow continuous blower setting (G)

5-Speed ECM Blower Motor

Model Motor Spd

Motor

Tap

T’Stat

Cnct.

Blower

Size

Motor

kW

Airflow (L/s) at External Static Pressure (Pa)

0

12.45 24.90 37.35 49.80 62.25 74.70

87.15

99.60 112.05 124.50 149.40 174.30 199.20 224.10 249.00

005

High

5

229 x 178

0.37

474

470

465

458

451

444

439

433

427

421

415

404

387

-

-

-

Med High

4

W

434

427

420

413

408

399

392

388

385

375

366

356

335

-

-

-

Med

3

406

401

396

387

380

373

366

359

352

346

340

319

283

-

-

-

Med Low

2

Y1

373

366

361

354

347

340

333

324

316

309

302

281

-

-

-

-

Low

1

G

309

293

278

267

257

248

241

223

205

189

-

-

-

-

-

-

006

High

5

W

229 x 178

0.37

512

507

500

493

486

479

474

467

463

455

448

437

408

385

-

-

Med High

4

Y2

465

458

451

444

437

429

425

418

411

404

399

382

370

356

-

-

Med

3

422

413

404

396

392

382

375

368

363

354

345

335

321

271

-

-

Med Low

2

Y1

380

370

363

356

347

342

335

326

316

309

304

288

257

-

-

-

Low

1

G

335

323

314

307

300

290

283

276

269

250

234

224

-

-

-

-

009

High

5

W

279 x 254

0.37

743

729

720

706

696

684

675

663

656

644

635

616

590

569

538

465

Med High

4

Y2

710

689

668

658

649

637

625

611

599

588

578

555

538

498

465

Med

3

Y1

694

668

644

621

604

592

583

573

564

550

538

512

484

420

-

-

Med Low

2

687

661

635

606

590

578

569

555

543

531

522

493

465

427

-

-

Low

1

G

635

609

583

545

517

479

444

432

420

382

356

-

-

-

-

-

012

High

5

W

279 x 254

0.75

913

904

899

887

875

866

854

847

842

833

826

812

793

772

750

739

Med High

4

857

843

831

819

812

802

798

788

781

772

762

746

729

710

694

675

Med

3

Y2

805

798

791

779

767

757

750

741

732

720

710

691

682

661

637

616

Med Low

2

Y1

760

748

739

729

724

710

696

689

682

673

663

639

623

611

588

559

Low

1

G

694

670

649

635

625

614

604

595

588

576

564

540

526

493

-

-

015

High

5

W

279 x 254

0.75

1074

1067

1060

1048

1041

1031

1022

1015

1008

998

991

979

958

939

918

892

Med High

4

Y2

1003

991

984

977

970

960

951

942

937

927

918

901

887

864

842

831

Med

3

934

923

916

906

901

890

880

871

864

854

847

828

812

795

774

757

Med Low

2

Y1

868

857

847

838

828

821

814

805

795

786

776

762

739

727

701

663

Low

1

G 805

793

783

769

762

755

748

736

727

720

713

694

673

644

621

599

017

High

5

W

279 x 254

0.75

1163

1156

1149

1137

1130

1121

1114

1104

1095

1088

1081

1062

1045

1017

979

927

Med High

4

Y1

1069

1060

1052

1045

1041

1029

1019

1012

1005

993

984

967

953

934

911

885

Med

3

1008

998

991

984

977

967

958

949

942

932

923

904

887

873

854

831

Med Low

2

946

937

932

923

916

906

899

887

878

866

857

842

824

812

786

767

Low

1

G

852

840

831

824

819

807

795

788

783

772

762

743

729

713

694

656

6/26/12

CAUTION: Disconnect all power before

performing this operation.

Setting Blower Speed - 5-Speed ECM

5-speed ECM blower motors have five (5) speeds of which

three (3) are selectable on single speed and four (4) are

selectable on dual capacity.

5-Speed ECM Motor Connections - Single Speed

5-Speed ECM Motor Connections - Dual Capacity

L

G

N

C

High Voltage
Connections

4.76 mm

1

2

3

4

5

G - Blue

Y1 - Red

AUX - Gray

C - Black

L - Orange
G - Green

N - Brown

Low Voltage

Connections 6.35 mm

L

G

N

C

1

2

3

4

5

AUX - Gray

G - Blue

Y1 - Red

Y2 - Tan

C - Black

L - Orange
G - Green

N - Brown

High Voltage
Connections

4.76 mm

Low Voltage

Connections 6.35 mm

Blower Performance Data