Appendix A: Configuration Information
A-3
User’s Manual Pub. 0300274-01 Rev. A.0
Environmental Tests
Industry Standards
Test Level Limits
Magnetic Field
(Performance Criteria
A)
IEC 61000-4-8
Rockwell Document QTP#X0327
30 Arms/m
AC Mains Voltage
Dips, Interruptions
and Variations
IEC 61000-4-11
Rockwell Document QTP#X0327
Follow the 61000-4-11.
Safety Tests and Test Limits
Safety Tests
Industry Standards
cUL
UL 508 Industrial Control Equipment Seventeenth Edition Dated
January 28 1999, with revisions through July 11, 2005 (ANSI/UL 508-
2005) (NRAQ, NRAQ7)
cUL CSA C22.2 No. 142 -M1987 Process Control Equipment May
1987
ULH ANSI/ISA–12.12.01–2007 Non-incendive Electrical Equipment
for Use in Class I, Division 2 Hazardous (Classified) Locations
CULH CSA C22.2 No. 213-M1987 - Non-incendive Electrical
Equipment for use in Class I Division 2 Hazardous Locations - March
1987
CE
CE LVD IEC 61131-2 Programmable Controllers Part 2: Equipment
Requirements and Tests; Second Edition 2003-02, Section 11-14
Performance Requirements
Input Specifications
Inputs per module
2 serial channels, non-concurrent operation
Interface, channel 1
RS-485, configurable during setup
Hardware flow control
None
Baud rates
9600, 19.2 k, 38.4 k, 76.8 k
Interface, channel 2
10/100M Ethernet, auto sensing
Crosstalk
-40 dB, minimum
Input protection
24 VDC continuous.
Power source
3.3 VDC and 24 VDC from backplane, 40 mA from 3.3 VDC
and 50 mA maximum from 24 VDC
Power, RTC Backup
72 hours, minimum
Accuracy, RTC Backup
+1.0,- 3.0 minutes/month.
Power consumption
<45 mA at 3.3 V, <55 mA at 24 V, <1.5 W Total
Inrush current
<500 mA at 3.3 V, <500 mA at 24 V