Chapter 3: Configuring the Module

3-19

User’s Manual Pub. 0300274-01 Rev. A.0

Each bit of the BACnet Binary Value represents a true/false value for one
BACnet Binary Value object. This block supports up to 64 such objects.

BACnet Analog Input 1 Block (0Ч100

– 0Ч1FF)

Register Name Addr.

Comments

Default

R/W

From PLC

R/W From
Module

BAC_AI_0

0Ч100

0Ч107

BACnet Analog Input tag 0

0

W

R

BAC_AI_1

0Ч108

0Ч10F

BACnet Analog Input tag 1

0

W

R

BAC_AI_31

0×1F8

0×1FF

BACnet Analog Input tag 31 0

W

R

This block is for the first 32 BACnet Analog Input tag values.

BACnet Analog Input objects are read from a user-specified PLC variable,
written by the PLC to the module, and then made available via the BACnet stack
as a read-only value.

BACnet Analog Input 2 Block (0Ч200

– 0Ч2FF)

Register Name Addr.

Comments

Default

R/W

From PLC

R/W From
Module

BAC_AI_32

0Ч200

0Ч207

BACnet Analog Input tag 32 0

W

R

BAC_AI_63

0×2F8

0×2FF

BACnet Analog Input tag 63 0

W

R

This block is for the last 32 BACnet Analog Input tag values.

BACnet Analog Output 1 Block (0Ч500

– 0Ч5FF)

Register Name Addr.

Comments

Default

R/W From PLC

R/W From Module

BAC_AO_0

0Ч500

0Ч507

BACnet Analog
Output tag 0

0

R

W

BAC_AO_1

0Ч508

0Ч50F

BACnet Analog
Output tag 1

0

R

W