Binary input-bacnetobjecttype = 3, Binary output-bacnetobjecttype = 4, Device-bacnetobjecttype = 8 – Spectrum Controls 2080sc-BAC User Manual
Page 44
4-2
Chapter 4: Implementing the BACnet Protocol
User’s Manual Pub. 0300274-01 Rev. A.0
Properties Supported
Property Data
Type Identifier
Read/Write
Event_State
BACnetEventState
36
R
Binary Input-BACnetObjectType = 3
Properties Supported
Property Data
Type Identifier
Read/Write
Object_Identifier
BACnetObjectIdentifier
75
R
Object_Name
CharacterString
77
R
Object_Type
BACnetObjectType
79
R
Present_Value
BACnetBinaryPV
85
R/W
Status_Flags
BACnetStatusFlags
111
R
Event_State
BACnetEventState
36
R
Out_Of_Service
BOOLEAN
81
R
Polarity
BACnetPolarity
84
R
Binary Output-BACnetObjectType = 4
Properties Supported
Property Data
Type Identifier
Read/Write
Object_Identifier
BACnetObjectIdentifier
75
R
Object_Name
CharacterString
77
R
Object_Type
BACnetObjectType
79
R
Present_Value
BACnetBinaryPV
85
R/W
Status_Flags
BACnetStatusFlags
111
R
Event_State
BACnetEventState
36
R
Out_Of_Service
BOOLEAN
81
R
Polarity
BACnetPolarity
84
R
Device-BACnetObjectType = 8
Properties Supported
Property Data
Type Identifier
Read/Write
Object_Identifier
BACnetObjectIdentifier
75
R
Object_Name
CharacterString
77
R
Object_Type
BACnetObjectType
79
R
System_Status
BACnetDeviceStatus
112
R
Vendor_Name
CharacterString
121
R