Chapter 3: Configuring the Module

User’s Manual Pub. 0300274-01 Rev. A.0

Examples: To write BO 3 present value to 1, do this – “bacwp 200121 4 3 85 15 -
1 9 1”

{param 1} – 200121. This is the module instance number.

{param 2} – 0. This is the object type. Object type is defined as: BI (3),
BO(4), AI(0), AO(1).

{param 3} – 3. This is the object instance.

{param 4} – 85. This is the property (present value 85, property array 87,
object name 77, object list 76).

{param 5} – 15. This is the priority. BACnet property write uses priority,
levels from 1 to 16. The module keeps a table for those priorities; high
priority overrides lower priority. So if there is a value in priority 14,
priority 15 value has no effect.

{param 6} – -1. This is the index. Use -1 for a single property write.

{param 7} – 9. Value type. Use 9 for BI and BO; use 4 for AI and AO.

{param 8} – 1. Value. This is the actual value to be written to the tag.

Section 3.6 Viewing Version Information

To view the current version of your software:

1. From the main software dialog, click Version Info:

The Version Info dialog appears:

The current software version is listed.

2. To exit, click OK.

Section 3.7 Viewing Log Information

To view current Log Information:

1. From the main software dialog, click Show Log:

The Log Data dialog appears: