Chapter 7: Testing Your Module

49

Channel Specific Errors
Note: n = channel number (0-7)

0x010(n)

Preset is defined larger than rollover limit for channel (n).

0x0200

Input Range mismatch for channel pair 0 and 1.

0x0202

Input Range mismatch for channel pair 2 and 3.

0x0204

Input Range mismatch for channel pair 4 and 5.

0x0206

Input Range mismatch for channel pair 5 and 7.

0x030(n)

Invalid operational mode for channel (n).

0x040(n)

Invalid storage mode for channel (n).

0x050(n)

Invalid input range for channel (n).

0x060(n)

Invalid signal filter for channel (n).

0x070(n)

RateSamplePeriod out of range for channel (n).

0x0800

Operational mode mismatch for channel pair 0 and 1.

0x0802

Operational mode mismatch for channel pair 2 and 3.

0x0804

Operational mode mismatch for channel pair 4 and 5.

0x0806

Operational mode mismatch for channel pair 6 and 7.

0x090(n)

Preset too high for channel (n).

0x0A0(n)

Count limit too high for channel (n).

0x0B0(n)

RateSamplePeriod not divisible by 10 for channel (n).

Note: If there are multiple errors in the configuration tags only one will be
displayed at a time. Once the displayed error has been corrected, the
additional errors will be displayed upon reconnection to the module. Each
error must be resolved before a running connection will be allowed.