ControlLogix

Counter Module

Fault information on the properties screen.

Determining Fault Type
When you are monitoring a module’s properties dialog in RSLogix 5000
and receive a fault message, the module fault area lists the type of fault.

Module

Configuration Errors

The “Additional Fault Code” value details the configuration error if the
“(16#0009) module configuration rejected: Parameter Error” was
received.

Global Errors
16#0F04 - .ConfigurationRevError

If the .ConfigurationRevNumber tag is 1 and a second owner
attempts to connect with a different configuration, this error
will occur. You must adjust the second owners configuration
to match the first.

16#0F05 - .ConfiguratinRevNumber Error

An invalid value has been entered into this tag.