Spectrum Controls 1756sc-CTR8 User Manual
Page 58

48
ControlLogix
™
Counter Module
Fault information on the properties screen.
Determining Fault Type
When you are monitoring a module’s properties dialog in RSLogix 5000
and receive a fault message, the module fault area lists the type of fault.
Module
Configuration Errors
The “Additional Fault Code” value details the configuration error if the
“(16#0009) module configuration rejected: Parameter Error” was
received.
Global Errors
16#0F04 - .ConfigurationRevError
If the .ConfigurationRevNumber tag is 1 and a second owner
attempts to connect with a different configuration, this error
will occur. You must adjust the second owners configuration
to match the first.
16#0F05 - .ConfiguratinRevNumber Error
An invalid value has been entered into this tag.