2/8

Form 916 (03.14) ©SOR Inc.

Physical Installation

 The 1710 must be mounted so that the centerline is within 3º of horizontal. The

conduit connection centerline must be within 3° of vertical and the nameplate at 12
o’clock. Switch actuation cannot be reversed by rotating the unit 180°.

 Pipe support hangers or stands should be used where necessary.
 All isolation valves must be fully open during service, as restricted valves may

cause erroneous level switching.

 Remember external chamber piping should be short, straight and unrestricted.
 Pipe must be of a diameter equal to or greater than the process connection

diameter.

 Valves and other equipment between the chamber and process must be of the same

diameter or larger than the process connection diameter to allow adequate liquid
flow into the chamber.

 Installation shall be carried out by suitably-trained personnel in accordance with the

applicable code of practice e.g. EN 60079-14.

Not following these installation instructions, including pipe and valve
diameter and pipe lengths can affect operation of the switch, including
differential.