beautypg.com

SOR Low Range User Manual

Page 4

background image

4/4

Form 492 (11.13) ©SOR Inc.

Calibration

14685 West 105th Street, Lenexa, KS 66215

 913-888-2630  800-676-6794 USA  Fax 913-888-0767

Registered Quality System to ISO 9001

Printed in USA

sorinc.com

Normal Calibration: Turn set point adjustment screw to move spring guide plate

into alignment with desired set point on calibration scale.

Precise Calibration: Device calibrated without reference to calibration scale

and low side vented.

Test apparatus: Manometer

Variable pressure source

Test light or ohmmeter

Connect variable pressure source to manometer and high side pressure port.

Connect test light or ohmmeter to C-Common and NO - Normally Open switching

element

contacts.

Raise pressure and note manometer reading when circuit closes.

Slowly drop pressure and note manometer reading when circuit opens.

Use a screwdriver to turn set point adjusting screw: counterclockwise to increase set

point, or clockwise to decrease set point.

Repeat steps 3, 4 and 5 until contacts change at desired increasing or decreasing

differential pressure set point.

Do not remove other covers or attempt to adjust other parts of the
mechanism. All have been precisely positioned at the factory and
should not be moved in the fi eld.