Calibration

Two calibration screws (zero and span) are located underneath the adjustment cover. (See

) Loosen the cover screws slightly (do not remove) and rotate the cover to reveal the

adjustment screws.

Numbers on the enclosure identify the adjustment screws: 1, 2 and 3.

Adjustment #1: Zero

Adjustment #2: Span

Adjustment #3: Not used

Unless specified otherwise, the transmitter is factory calibrated to 1 VDC @ 0 psi and 5
VDC at the top of the adjustable range specified on the nameplate.

Calibration Procedure
The zero and span calibration procedure should be performed under ambient process
temperature conditions.

A pressure source with a calibrated reference gage, a voltmeter and a DC voltage supply are
required. (See

) Note the adjustable range on the instrument nameplate. For both zero

and span adjustments, turn the adjustment screw clockwise to increase, counterclockwise
to decrease.

Connect the transmitter as shown in

. The case ground must be connected to the

earth ground.

Apply pressure at which 1 VDC output is desired. (Zero may be adjusted + 10% of the

Upper Range Limit.)

With the pressure source steady at the desired zero level, rotate the zero adjustment

(#1) for a 1 VDC indication on the voltmeter.

Apply pressure at which 5 VDC output is desired. The span may be adjusted from 20 to

100% of the upper range limit specified on the nameplate. (Maximum turndown is 5:1.)

With the pressure source steady at the desired span level, rotate the span adjustment

(#2) for a 5 VDC indication on the voltmeter.

Repeat Steps 2 through 5 as needed if offsetting 1 VDC from the normal zero point.