Electrical termination – SOR 536CR Low Power Pressure Transmitters User Manual
Page 2
2/8
Form 921 (03.13) ©SOR Inc.
Electrical Termination
Making the Electrical Connection First
The electrical connection may be installed on an adequately supported rigid conduit
system. Use suitable locknuts (not provided) when mounting the instrument to an
unthreaded (knockout) hole. Process connection pipe or tubing may be rigid or flexible.
Securely connect the conduit pipe or fitting by holding the hex on the electrical connection
while tightening.
Units in hazardous locations – prior to removal from service, make sure
that the work area is declassifi ed. Failure to do so could result in severe
personal injury or substantial property damage.
Three-conductor shielded cable is provided as standard. If the optional screw terminal
housing was specified, wire according to screw terminal designation below.
Wire Lead Color
Optional Terminal
Designation
Connection
Red
+
10-30 VDC power supply
Black
-
Power supply return
White
1-6 VDC
1-5 VDC output (with respect
to power supply return)
(shield)
GND
(ease ground) should be
connected to earth ground
Zero
Span
Not Used
Volt meter
1 - 5 VDC
Power supply
10-30 VDC
Case
Ground
Red
Black
White
Shield