SOR 534HS Two-Wire Pressure Transmitters User Manual
Page 3
Form 953 (03.13) ©SOR Inc.
3/12
Power
Supply
11 - 30 VDC
milliammeter 4 -
20 mA
Black
Case
Ground
Zero
Not Used
Span
Bare
Red
A pressure source with a calibrated reference gage, a milliammeter and a DC voltage supply
are required. Note the adjustable range on the instrument nameplate. For both zero and span
adjustments, turn the adjustment screw clockwise to increase, counterclockwise to decrease.
Connect the transmitter as shown in
. Case ground must be connected to earth
ground to ensure EMI/RFI protection.
Apply pressure at which 4 mA output is desired. (Zero may be adjusted +10% of the
upper range limit.)
When zero is elevated above 0 psi, maintain 80% of the range of the transmitter range
between the 4 mA and 20 mA points.
With pressure source steady at the desired zero level, rotate the zero adjustment (#1)
for a 4 mA indication on the milliammeter.
Apply pressure at which 20 mA output is desired. Span may be adjusted from 20 to
100% of the upper range limit. (Maximum turndown is 5:1.)
With pressure source steady at the desired span level, rotate the span adjustment (#3)
for a 20 mA indication on the milliammeter.
Repeat Steps 2 through 6 as needed if offsetting 4 mA from the normal zero point.
If interaction occurs, turn zero and span 15 turns counterclockwise. Repeat Steps 2
through 7 above.