SOR 534HS Two-Wire Pressure Transmitters User Manual

Page 3

background image

Form 953 (03.13) ©SOR Inc.

3/12

Power

Supply

11 - 30 VDC

milliammeter 4 -

20 mA

Black

Case

Ground

Zero

Not Used

Span

Bare

Red

A pressure source with a calibrated reference gage, a milliammeter and a DC voltage supply
are required. Note the adjustable range on the instrument nameplate. For both zero and span
adjustments, turn the adjustment screw clockwise to increase, counterclockwise to decrease.

Connect the transmitter as shown in

. Case ground must be connected to earth

ground to ensure EMI/RFI protection.

Apply pressure at which 4 mA output is desired. (Zero may be adjusted +10% of the

upper range limit.)

When zero is elevated above 0 psi, maintain 80% of the range of the transmitter range

between the 4 mA and 20 mA points.

With pressure source steady at the desired zero level, rotate the zero adjustment (#1)

for a 4 mA indication on the milliammeter.

Apply pressure at which 20 mA output is desired. Span may be adjusted from 20 to

100% of the upper range limit. (Maximum turndown is 5:1.)

With pressure source steady at the desired span level, rotate the span adjustment (#3)

for a 20 mA indication on the milliammeter.

Repeat Steps 2 through 6 as needed if offsetting 4 mA from the normal zero point.

If interaction occurs, turn zero and span 15 turns counterclockwise. Repeat Steps 2
through 7 above.