SOR Dual Hi-Lo Weatherproof Pressure Switch User Manual
Page 4
4/4
Form 248 (04.13) ©SOR Inc.
14685 West 105th Street, Lenexa, KS 66215
913-888-2630 800-676-6794 USA Fax 913-888-0767
Registered Quality System to ISO 9001
Printed in USA
www.sorinc.com
Calibration
Remove the housing cover.
To increase the set point at which the No. 1 (left side) switching element(s) actuates,
turn the hex adjusting nut clockwise with a 3/4-inch open-end wrench.
Sight across the flat top of the adjusting nut to the calibration scale at the bottom of
the housing for an approximate set point. Use a 1/4% external pressure gauge to more
precisely calibrate the pressure switch.
Repeat steps
and
for the No. 2 (right side) set point. There is no interaction, so it
is not critical whether the left or right side is set first.
Replace the housing cover. The pressure switch can be placed in service.
Overtravel has been preset at the factory, i.e. the switching element assembly has
been precisely positioned in the housing for optimum performance. It normally
should not be changed in the fi eld. Should adjustment be necessary, factory
approved procedures must be closely followed. Any inadvertent movement or
replacement in the fi eld will degrade performance, void the warranty and could
render the device inoperative.
“V2 EXPLOSION PROOF 18”
18 AWG color-coded and marked wire leads
with 3/4” NPT (F) conduit connection.
Common
Normally Open
Normally Closed
SPDT
No. 1 (Left side)
C1 Blue
NO1 Black
NC1 Red
No. 2 (Right side)
C2 Blue
NO2 Black
NC2 Red
2-SPDT (DPDT)
Nos. 1 & 2 (Left side)
C1 Blue
NO1 Black
NC1 Red
C2 Yellow
NO2 Brown
NC2 Orange
Nos. 3 & 4 (Right side)
C3 Blue
NO3 Black
NC3 Red
C4 Yellow
NO4 Brown
NC4 Orange
GR - Ground (Earth) Green wire connected to each hermetically sealed switching
element capsule.
NOTE: Transpose NO and NC on vacuum switches when set points are in the vacuum range.