beautypg.com

Maintenance, 1 servicing, 2 spark electrode – Glow-worm Flexicom sx User Manual

Page 30

background image

0020107231_04 - 12/14 - Glow-worm

MAINTENANCE

- 30 -

15585

Diagram 12.4

Diagram 12.5

12813

15586

12.1 Servicing

NOTE: If the Combustion CO2, CO/CO2 ratio & Gas rate

checks did not require adjustment then it will not be necessary

to complete a full service.

For routine servicing requirements, remove the front casing

panel, see diagram 13.2, and hinge down the control panel.

Before commencing with a service or replacement of parts.

The boiler should be isolated from the electrical and gas

supplies.

12.2 Spark Electrode

NOTE: If the functional checks did not indicate poor

combustion then it is not necessary to service this

component.

Ease the securing clips away from the sump to release the

retaining catch then push the flue hood up to disengage from

the sump, see diagram 12.4.

To remove, swivel flue hood 90

o

and pull down and out, see

diagram 12.4.

Check seal for wear or damage and replace if necessary.

IMPORTANT: Do not allow fixings, nuts, screws, etc. to fall

into the open flue hood sump, use a temporary cover whilst

removing any parts.

Disconnect the spark electrode plug and earth lead. Remove

the two securing screws and withdraw the spark electrode

carefully from the combustion chamber, see diagram 12.5.

Inspect the tips for damage.

Clean away any debris and check the spark gap is 4mm.

Check the electrode gasket for signs of damage and replace if

necessary.