beautypg.com

Maintenance, 12 servicing general inspection – Glow-worm Flexicom sx User Manual

Page 28

background image

0020107231_04 - 12/14 - Glow-worm

MAINTENANCE

- 28 -

IMPORTANT NOTES:

1. To ensure the continued efficient and safe operation of the boiler it is recommended that it is checked and

serviced at regular intervals. The frequency of servicing will depend upon the particular installation and usage,

but in general once a year should be enough.

2. It is the Law that any servicing is carried out by a

competent person approved at the time by the Health and

Safety Executive.

3. Before commencing with a service or replacement of parts the boiler should be isolated from the electrical

supply and the gas supply should be turned off at the gas service isolation valve.

4. When replacing a part on this appliance, use only spare parts that you can be assured conform to the safety

and performance specification that we require. Do not use reconditioned or copy parts that have not been

clearly authorised by Glow-worm.

5. If any electrical connections have been disconnected and after their connection, checks to the earth continuity,

polarity, short circuit and resistance to earth must be repeated using a suitable multimeter, as described in

section 13.

6. After servicing, complete the relevant Service Interval Record section of the Benchmark Checklist located in the

inside back pages of this document.

12 Servicing

General Inspection

Prior to, during servicing and after any maintenance or changed

parts, the following must be checked.

● The integrity of the flue system and flue seals.

● The integrity of the appliance combustion circuit and relevant

seals.

● Electrical, gas and water connections.

● System pressure.

● the combustion performance, refer to the following procedure.

● The operational gas inlet pressure and gas rates, refer to the

commissioning section paragraph 11.5.

Correct any fault before continuing.

COMPETENCY TO CARRY OUT THE CHECK OF

COMBUSTION PERFORMANCE

NOTE: BS 6798: 2009 Specification for installation and

maintenance of gas-fired boilers of rated input not exceeding

70kW net advises that:

● The person carrying out a combustion measurement must be

assessed as competent in the use of a flue gas analyser and

the interpretation of the results.

● The flue gas analyser used should be one meeting the

requirements of BS7927 or BS-EN50379-3 and be calibrated in

accordance with the analyser manufacturers’ requirements.

● Competence can be demonstrated by satisfactory completion

of the CPA1 ACS assessment, which covers the use of

electronic portable combustion gas analysers in accordance

with BS 7967, parts 1 to 4.

● Ensure that the gas analyser is set to the correct fuel setting.

● Select the “

°C

bar

”, constant central heating function by pressing

the “Mode” button repeatedly, refer to

commissioning section. The boiler should fire automatically.

NOTE: Safe combustion can only be verified by measuring CO/

CO2 ratio. This must not exceed the value shown in the table

opposite.

13948

Diagram 12.1

13028

COMBUSTION CHECK AND SETTING THE AIR/

GAS RATIO VALVE

● Remove the front casing panel, see diagram 12.2 and hinge

down the control box. Taking care not to touch any internal

components, proceed as follows:

● Connect the CO2 combustion analyser to the relevant test

point, see diagram 12.1.