Installation, Multiple boiler chimney flue length, Flexicom 18sx flexicom 30sx – Glow-worm Flexicom sx User Manual
Page 13
![background image](/manuals/736779/13/background.png)
0020107231_04 - 12/14 - Glow-worm
INSTALLATION
- 13 -
4.2.4
Multiple boiler chimney flue
Ø 60/100 mm (C43 type installation)
The flue connecting from the appliance to
the flue system must be supplied from the
manufacturer of the boiler.
C43 flue systems must not be a 'pressurised
system' but act under natural draught
principles
C43 type flue systems must have their
own condensate drain fitted and not allow
condensate to mix into other appliances
Multiple Boiler Chimney Flue Length
The flue length must be calculated and installed according to
the relevant standards EN 13384-1 and 2 (C43 flue systems
only) with reference to the table below and the manufacturers
instructions supplied.
The appliance maximum flue length must be included when
calculating the overall design of the flue system.
NOTE: The horizontal flue terminal must be removed.
L
B
A
1
2
3
4
5
Key
1 Pressure balancing system
2 Air-inlet pipe
3 Collector pipe
4 Boiler
5 Inspection hatch
A Final storey
B Ground floor
Type
Max length (L)
Ø 60/100
8 m
Each time an additional 90° bend is necessary (or 2 at 45°), the
length (L) must be reduced by 1 m.
Flexicom
18sx
Flexicom
30sx
Exhaust mass rate (g/s)
At Min Thermal
Load (40C°/30°C)
4.26
4.26
At Max Thermal
Load (80C°/60°C)
8.24
13.95
Exhaust temperature (ºC)
At Min Thermal
Load (40C°/30°C)
33.2
33.2
At Max Thermal
Load (80C°/60°C)
63.0
87.4