Installation, 7 vented dhw system, 8 unvented dhw system – Glow-worm Flexicom sx User Manual
Page 16: 10 safety valve, 11 expansion vessel
![background image](/manuals/736779/16/background.png)
0020107231_04 - 12/14 - Glow-worm
INSTALLATION
- 16 -
15723
Diagram 5.3
Water System - Domestic Hot Water
5.6 Domestic Water Cylinder
SINGLE FEED INDIRECT CYLINDERS ARE NOT SUITABLE
AND SHOULD NOT BE USED.
The domestic hot water cylinder must be of the double feed
indirect coil type. It must be suitable for working at a gauge
pressure of 0.35bar above the safety valve setting.
5.7 Vented DHW System
General - All domestic hot water circuits, connections, fittings
must be in accordance with the relevant standards and water
supply regulations.
For GB: Guidance G17 to G24 and recommendation R17 to
R24 of the Water Regulations Guide
(for Scotland, the Water
Byelaws 2000, Scotland)
.
For IE: The current edition of I.S.813 “Domestic Gas
Installations”.
5.8 Unvented DHW System
General - All domestic hot water circuits, connections, fittings
must be in accordance with the relevant standards and water
supply regulations.
For GB: Guidance G17 to G24 and recommendation R17 to
R24 of the Water Regulations Guide.
For IE: The current edition of I.S.813 “Domestic Gas
Installations”.
Where a storage system will not have a vent to atmosphere
the installation must comply with the building regulations and
the Water Supply (water fittings) Regulations 1999 and water
byelaws 2000, Scotland
, see also the current issue of BS5546
and BS6700.
If fitting to an existing system the local authority should be
informed.
Water System - Sealed Central Heating
System
5.9 Sealed Water Systems
The installation must comply with the appropriate requirements
of the current issue of BS4814, BS5449, BS6759, BS6798 and
BS7074 Part 1 and 2.
See diagram 5.4 for a suggested layout.
5.10 Safety Valve
The safety valve is an integral part of the boiler and it cannot
be adjusted.
The pipe from the safety discharge valve must
not discharge above an entrance, window or any type of public
access area.
5.11 Expansion Vessel
The boiler has an integral expansion vessel with a capacity of 8
litres (1.76 gallons), with a charge pressure of 0.5bar.
NOTE: The expansion vessel volume depends on the total
water system volume and the initial system design pressure.
In GB, Guidance on vessel sizing is also given in the current
issue of BS5449 and BS7074 Part 1.
In IE, current edition of I.S.813 “Domestic Gas Installations”