Installation – Glow-worm Flexicom hx User Manual
Page 9

0020107230_04 - 12/14 - Glow-worm
INSTALLATION
- 9 -
3 Boiler Location, Clearances and 
Ventilation
3.1 Location
This boiler is not suitable for outdoor installation.
This boiler may be installed in any room, although particular 
attention is drawn to the installation of a boiler in a room 
containing a bath or shower where reference must be made to 
the relevant requirements.
This boiler is suitable for installation in bathroom zones 2 and 3. 
In GB this is the current I.E.E. WIRING REGULATIONS and 
BUILDING REGULATIONS.
In IE reference should be made to the current edition of I.S.813 
“Domestic Gas Installations” and the current ETCI rules.
 
3.2 Clearances
The boiler should be positioned so that at least the minimum 
operational and servicing clearances are provided, see diagram 
3.1.
Increased clearances would be benefi cial for the installation.
Where external access is not practicable, for fl ue installations 
consideration should be given for the space required to insert the 
fl ue internally, which may necessitate the clearance to be greater 
than those specifi ed in diagram 3.1.
3.3 Timber Frame Buildings
If the boiler is to be installed in a timber frame building it should 
be fi tted in accordance with the Institute of Gas Engineers 
document IGE/UP/7/1998. If in doubt seek advice from the local 
gas undertaking or Glow-worm.
3.4 Combustible Material
The boiler and fl ue are suitable for installation onto and through 
combustible materials provided that:-
1) Minimum 5mm clearance is maintained around the 
circumference of the fl ue (air intake).
2) The combustible surface and fi xings are suitable for 
supporting the load.
3) The minimum clearances from the boiler case are 
maintained.
3.5 Room Ventilation
The boiler is room sealed so a permanent air vent is not required.
3.6 Cupboard or Compartment Ventilation
Due to the high effi ciency and hence low casing temperature of 
this boiler, cupboard or compartment ventilation is not necessary.
Leave existing air vents.
12792
Diagram 3.1
