INSTALLATION
- 15 -
• Where possible keep the existing boiler/circulating pump in
place when fl ushing the system
5.6.2 Flushing the system
• Fill the system with cold water and check for leaks.
• Open all drain cocks and drain the system.
• Close drain cocks and add a suitable fl ushing agent (cleaner)
compatible with Aluminium at the correct strength for the 
system conditions in accordance with the manufacturer’s 
instructions.
Examples of suitable fl ushing agents/cleansers are:
Sentinel X300, X400
Fernox F3
• Circulate
the
fl ushing agent before the boiler is fi red up.
• Run the boiler/system at normal operating temperature as
directed by the manufacturer of the fl ushing agent.
• It is essential to drain and thoroughly fl ush the whole system
to remove the fl ushing agent and debris.
• It may be necessary to use a power fl ushing machine to aid
the cleansing procedure in some circumstances.
• Close the drain cocks and refi ll with fresh water and a
suitable inhibitor.
• Vent any air from the boiler and system.
5.6.3 Inhibiting the system
Add a suitable inhibitor or combined inhibitor/anti-freeze, if the 
system is exposed to freezing conditions, to the heating system 
in accordance with the DWTA code of practice and inhibitor 
manufacturer’s guidelines.
Examples of suitable inhibitors are:
Sentinel X100
Fernox protector F1
Artifi cially softened water must not be used to 
fi ll the central heating system.
Sealing agents - The addition of sealing agents 
to the system water is not permitted as this can 
cause problems with deposits left in the heat 
exchanger.