Installation – Glow-worm Flexicom hx User Manual
Page 16

0020107230_04 - 12/14 - Glow-worm
INSTALLATION
- 16 -
Water System - Domestic Hot Water
5.7 Domestic Hot Water Cylinder
SINGLE FEED INDIRECT CYLINDERS ARE NOT SUITABLE
The domestic hot water cylinder must be of the double feed fully 
indirect coil type.
5.8 Unvented DHW System
General - All domestic hot water circuits, connections, fi ttings 
must be in accordance with the relevant standards and water 
supply regulations.
For GB: Guidance G17 to G24 and recommendation R17 to 
R24 of the Water Regulations Guide 
(for Scotland, the Water
Byelaws 2000, Scotland)
.
Document G Sanitation, hot water safety and water effi ciency, 
section 3 of the building regulations, requires that the 
installation of an unvented system should be notifi ed to the local 
authority Building Controls Department and that the work must 
be carried out by a competent person approved at the time by 
the Health and Safety Executive, as defi ned in the approved 
document G3.
For IE: The current edition of I.S.813 “Domestic Gas 
Installations”.
Where a storage system will not have a vent to atmosphere 
the installation must comply with the building regulations and 
the Water Supply (water fi ttings) regulations 1999 and water 
byelaws 2000, Scotland, see also the current issue of BS5546 
and BS6700.
If fi tting to an existing system the local authority should be 
informed.
5.9 Vented DHW System
General - All domestic hot water circuits, connections, fi ttings 
must be in accordance with the relevant standards and water 
supply regulations.
For GB: Guidance G17 to G24 and recommendation R17 to 
R24 of the Water Regulations Guide 
(for Scotland, the Water
Byelaws 2000, Scotland)
.
For IE: The current edition of I.S.813 “Domestic Gas 
Installations”.
Water System - Open (Vented) Central 
Heating System
5.10 Open (Vented) Central Heating System
The boiler must be supplied from an unrestricted water supply 
taken from a feed and expansion cistern situated at a maximum 
height of 27 metres (90ft) above the boiler.
The cold feed must be 15mm minimum size.
The vent must rise continuously and be unrestricted.
It is important that the relative positions of the pump, cold feed 
and open vent are as shown in diagram 5.3.
5.11 Combined Feed and Vent
For combined feed and vent, a 22mm pipe must be fi tted in 
accordance with BS 5449.
Diagram 5.3
15726
