The PGD3-IR instrument is fitted with miniature infrared sensors for the detection of flammable gases (except hydrogen) and carbon
dioxide. The instrument can house up to 2 infrared sensors. They are ‘EEx d’ certified types and must only be replaced with sensors
labelled with the certification details stated in section 2 of this manual.
The flammable sensors are non-selective that is, they will detect a range of hydrocarbon gases. However, during manufacture of the
PGD3-IR instrument the sensors are calibrated to methane. See Section 6.11 for relative responses for other hydrocarbon gases.

10.1.1

LEL Flammable Sensor Specification

Gases detected

Various combustible gases and vapors

Range

0 100% LEL

Resolution

1% LEL

Operating Voltage

3 to 5 Volts dc

Operating Current

80 mA

T

90

Response Time

< 30 Seconds

Linearity

Linear 0-100% LEL Methane

Long Term Sensitivity

1% LEL / month

Long Term Zero Drift

< 3% LEL / year

10.1.2

0-100% Volume Flammable Sensor Specification

Gases detected

Methane

Range

0 100% Volume

Resolution

0.05% Volume

Operating Voltage

3 to 5 Volts dc

Operating Current

80 mA

T

90

Response Time

< 30 Seconds

Linearity

Linear 0 - 100% Volume Methane

Sensitivity Drift

< 5% volume methane / month

Range Changing

Automatically carried out by the instrument

10.1.3

Carbon Dioxide Sensors

Range

0 5% Volume CO

2

Resolution

1% LEL

Operating Voltage

3 to 5 Volts dc

Operating Current

80 mA

T

90

Response Time

< 30 Seconds

Linearity

Linear 0 - 5% CO

2

Zero Drift

+/ 500ppm / month