Two pump modes are available:

1.

Pump Mode = 0 ‘CH or CH&DHW’

• In this mode either CH or DHW pump terminal is energized

depending on type of demand (CH or DHW).

• CH and DHW pumps are never energized at the same time.

• In the case of simultaneous call for both CH and DHW, the

energized pump depends on whether the boiler is currently

supplying CH or DHW demand. Refer to DHW Priority

settings below.

• This is typical of hydronic system design with separate CH

and DHW Pumps.

2.

Pump Mode = 4 ‘System Pump’

• In this mode only one external system pump is installed in

hydronic system. This pump will energize independent of

type of demand (CH or DHW).

• Connect this pump to CH/System Pump electrical terminal

block. See page

35 for diagram.

• DHW pump terminal does not function.

• This is typical of hydronic system design which utilizes zone

valves for all CH zones and DHW indirect tank.

Note:

• Pump Mode selection depends on electrical and

hydronic system design. Please refer to sections 5

and 8 for recommended hydronic piping and electrical

configurations.

• Internal heat exchanger pump is energized anytime

demand exists regardless of Pump Mode setting or type

of demand (CH or DHW).

'Service Reminder’ feature allows the installer to enable or

disable a service reminder notification on the User Interface at a

predefined interval .
Service reminder does not affect operation of boiler in any way.

It is only a reminder to End User that routine preventative

maintenance is required by qualified service technician.
Allowed Range: 1 to 999 days