beautypg.com

15 - glossary – Dunkirk Helix VX Vertical Laser Tube Wall Hung Stainless Steel Modulating Condensing Boiler User Manual

Page 68

background image

68

NATURAL GAS

Length of Pipe

- Ft.

Pipe Capacity - BTU Per Hour Input Includes Fittings

1/2”

3/4”

1”

1 1/4”

20

92,000

190,000

350,000

625,000

40

63,000

130,000

245,000

445,000

60

50,000

105,000

195,000

365,000

PROPANE GAS

Length of Pipe

- Ft.

Pipe Capacity - BTU Per Hour Input Includes Fittings

Copper Tubing

(Outside Diameter)

Iron Pipe

5/8”

3/4”

1/2”

3/4”

20

131,000

216,000

189,000

393,000

40

90,000

145,000

129,000

267,000

60

72,000

121,000

103,000

217,000

• ANSI - American National Standards Institute, Inc.

oversees creation and maintenance of voluntary

consensus standards, including ANSI Z21.13/CSA 4.9:

Gas-Fired Low Pressure Steam and Hot Water Boilers.

• ASTM - American Society for Testing and Materials.

ASTM International is one of largest voluntary standards

development organizations in world trusted source for

technical standards for materials, products, systems,

and services. Known for their high technical quality and

market relevancy, ASTM International standards have

important role in information infrastructure that guides

design, manufacturing and trade in the global economy.

• AUTHORITY HAVING JURISDICTION - Individual

or organization adopting and enforcing codes, rules,

and by-laws governing various concerns of community.

Commonly referred to as "final authority" for any matters

relating to LIFE SAFETY and BUILDING CONSTRUCTION

within a community.

• Btu - Abbreviation for British Thermal Unit. Quantity of

heat required to raise temperature of 1 pound of water

1°F.

• BURNER - Device for final conveyance of gas or mixture

of gas and air, to combustion zone.

• COMBUSTION - Rapid oxidation of fuel gases

accompanied by production of heat or heat and light.

Complete combustion of fuel is possible only in presence

of adequate supply of oxygen.

• COMBUSTIBLE MATERIAL - Materials made of or

surfaced with wood, compressed paper, plant fibers,

or other materials capable of being ignited and

burned. Such material shall be considered combustible

even though flame-proofed, fire-retardant treated, or

plastered.

• CONDENSATE - Liquid separated from flue gas due to

reduction in temperature.

• DIRECT VENT BOILER - Boiler constructed and installed

so all combustion air is derived directly from outdoors

and all vent gases are discharged to outdoors.

• DRAFT - Pressure difference causes gases or air to flow

through a chimney, vent, flue or appliance.

• FLA - Full load amps.

• FLUE GASES - Products of combustion plus excess air

in appliance flues or heat exchanger.

• HIGH-VOLTAGE - Circuit involving potential of not

more than 600 volts and having circuit characteristics in

excess of those of low-voltage circuit.

• IGNITER - Device utilizing electrical energy to ignite

gas at main burner.

• LEAK CHECK - Operation performed on gas piping

system to verify system does not leak.

• LOW WATER CUTOFF - Device constructed to

automatically cut off fuel supply when surface of water in

boiler falls to lowest safe water level.

• LOW-VOLTAGE - Circuit involving potential of not more

than 30 volts.

• METRIC GAS METERS

MBH

=

127,116 x cu meters
Seconds

For example: Gas Meter measures 0.1 cubic Meters in 100

seconds

MBH

=

127,116 x 0.1

= 127 MBH

100

• PRESSURE TEST - Operation performed to verify gas

tight integrity of gas piping following its installation or

modification.

• PURGE - To free gas conduit of air or gas, or mixture of

gas and air.

• PURGE TIME - Period of time intended to allow for

dissipation of any unburned gas or residual products of

combustion.

• GAS PIPE SIZES - Table 14

15 - GLOSSARY