12.1 Ratings and Capacities

• Constructed and hydrostatically tested for maximum

allowable working pressure of 150 psig (pounds per

square inch gauge) (1035 kPa) in accordance with ASME

Boiler and Pressure Vessel Code, Section IV, Rules for

Construction of Heating Boilers.

• Ratings used for elevations up to 2000 ft (600m) above

sea level.

• For elevations between 2000 ft (600m) and 4500 ft

(1350m), install high altitude control kit

• For elevations above 4500 ft (1350m) install high

altitude control kit and :

• USA - Reduce input rate 4% for each 1000 ft

(300m) beyond 4500 ft.

• Canada - Contact Provincial authority having

jurisdiction for installations above 4500 feet (1350

m) above sea level.

SEA LEVEL RATINGS

NATURAL AND PROPANE GASES

Size

Boiler Input Rate

(MBH)

(1)

Heating

Capacity

(MBH)

(1)(2)

Net AHRI

Rating, Water

(MBH)

(1)(3)

AFUE

(2)

Maximum

Minimum

050

50

10

46

40

95.0

075

75

15

69

60

95.0

100

100

20

91

79

95.0

150

150

30

139

121

95.0

200

200

40

185

161

95.0

(1)

1000 Btu/hr (British Thermal Units Per Hour)

(2)

Heating Capacity and AFUE (Annual Fuel Utilization Efficiency) are based on DOE (Department of Energy) test

procedures.

(3)

Net AHRI Ratings based on piping and pickup allowance of 1.15. Contact Technical Support before selecting boiler for

installations having unusual piping and pickup requirements, such as intermittent system operation, extensive piping systems,

etc.

12 - RATINGS AND CAPACITIES

Table 13 - Sea Level Ratings