15 read leading code setting – ADLINK ND-6063 User Manual
Page 94
86
• Command Set
3.15 Read Leading Code Setting
( 6050, 6052, 6053, 6054,
6056, 6058, 6060, 6063 )
@Description
Read command leading code setting and host watchdog status.
@Syntax
~(Addr)0
~
Command leading code.
(Addr)
Address ID
0
Read command leading code setting.
@Response
!(Addr)(Status)(C1)(C2)(C3)(C4)(C5)(C6)
or
?(Addr)
!
Command is valid.
?
Command is invalid.
(Addr)
Address ID
(Status)
(2-character)
Bit 0 : Reserved
Bit 1 : Power failure or watchdog failure
Bit 2 : Host watchdog is enable
Bit 3 : Host failure
(C1)
Leading code 1, for read configuration status,
firmware version, etc. default is $.
(1-character)
(C2)
Leading code 2, for read synchronize sampling,
digital output ,default is #. (1-character)
(C3)
Leading code 3, for change configuration.
default is %. (1-character)
(C4)
Leading code 4, for read alarm status, enable
alarm, etc. default is @. (1-character)
(C5)
Leading code 5, for read command leading
code, change command leading code, etc.
default is ~. (1-character)
(C6)
Leading code 6, this leading code is reserved.