• Command Set

3.3

Set Configuration

( 6050, 6052, 6053, 6054,

6056, 6058, 6060, 6063 )

@Description

Configure the basic setting about address ID, baud rate, and checksum.

@Syntax

%(OldAddr)(NewAddr)(TypeCode)(BaudRate)(CheckSumFlag)

%

Command leading code.
(1-character)

(OldAddr)

NuDAM module original address ID. The
default address ID of a brand new module is
01. The value range of address ID is 00 to FF in
hexadecimal. (2-character)

(NewAddr)

New address ID, if you don’t want to change
address ID , let new address ID equals to the
old one. (2-character)

(TypeCode)

Type Code is fixed 40H for Digital I/O modules .
(2-character)

(BaudRate)

Communication baud rate, refer to Table 3-1
for details. (2-character)

(CheckSumFlag)

Define check-sum status, refer to Table 3-2 for
details. (2-character)

@Response

!(Addr)

or

?(Addr)

(Addr)

Address ID.

!

Command is valid.

?

Command is invalid. Invalid parameter values,
When you wanted to change the setting without
grounding the DEFAULT* pin.