beautypg.com

4 read configuration – ADLINK ND-6063 User Manual

Page 72

background image

64

• Command Set

3.4

Read Configuration

( 6050, 6052, 6053, 6054,

6056, 6058, 6060, 6063 )

@Description

Read the configuration of module on a specified address ID.

@Syntax

$(Addr)2

$

Command leading code

(Addr)

Address ID.

2

Command code for reading configuration

@Response

!(Addr)(TypeCode)(BaudRate)(CheckSumFalg)

or

?(Addr)

!

Command is valid.

?

Command is invalid.

(Addr)

Address ID.

(TypeCode)

It always be 40 (Hex) for digital I/O modules.

(BaudRate)

Current setting of communication baud rate,
refer to Table 3-1 for details.

(CheckSumFlag)

Current setting of check-sum flag, refer to
Table 3-3. for details.