beautypg.com

Table iv—manifold pressure (inches w.c.), Adjusting pressure regulator, Checking propane gas input – Bryant 479 D User Manual

Page 7: Burner adjustment, Viii. furnace operation

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

Gas input of the furnace and each chiller must be

checked and adjusted if necessary to agree with that

shown on the rating plates. The burners are equipped

with fixed orifices.

CAUTION: The chillers may be run for short periods

with the panels removed. Prolonged operation with

panels removed should be avoided.

Natural gas units are equipped with adjustable gas

pressure regulators. Propane gas units are not equip­

ped with a pressure regulator.

One of the following two methods may be used to

check natural gas input on both the furnace and

chillers.

Adjusting Gas Input

A. Measuring Gas Flow at Meter

All gas appliances must be turned off except the bur­

ners on the manifold being checked when measuring

the gas flow at the meter to adjust the gas input.

Proceed as follows:

1. Determine the number of seconds required for the

gas meter test dial to complete one revolution.

2. Divide 3600 by the number of seconds in Step 1.

3. Multiply the result in Step 2 by the number of

cubic feet of gas flow per hour.

4. Multiply the result of Step 3 by the Btu heating

value of the gas (consult local utility for value). This

is the total measured Btu/hr input.

Compare this value with the one shown on the rating

plate.

Example: Suppose the size of the test dial is 5 cu. ft.;

it takes 40 seconds for the dial to complete one

revolution; heating value of the gas is 1050 Btu/cu. ft.

Proceed as follows:

40 seconds to complete one revolution

3600 divided 40 equals 90

90

X

5 - 450 cu. ft. per hour of gas flow

450

X

1050 - 472,5000 Btuh input

Only minor changes should have to be made at the

pressure regulator to bring it within the rated input of

the unit. If the manifold pressure must be changed

more than 0.3” w.c. to obtain the rated input, the

orifices should be changed accordingly.

B. Using Water Manometer

Proceed as follows when using a water manometer to

measure the manifold pressure when adjusting the gas

input:

1. Connect a water manometer to the 1/8” pressure

tap on the manifold or gas valve.

2. With the burners fired, set the correct manifold

pressure as shown in Table IV. Check with the gas

utility for the Btu valve and specific gravity of gas in

the area.

TABLE IV—MANIFOLD PRESSURE

(Inches

W.C.)

Specific Gravity

0.59

0.61

0.63

0.65

0.67

900

3.9”

4.0”

4.1”

4.2”

4.3”

950

3.5”

3.6”

3.7”

3.8”

3.9”

1000

3.1”

3.2”

3.3”

3.4”

3.5”

1025

3.0”

3.1”

3.2”

3.3”

3.4”

1050

2.8”

2.9”

3.0”

3.1”

3.2”

1100

2.6”

2.7”

2.8”

2.9”

3.0”

Adjusting Pressure Regulator

If the measured and rated input are not ap­

proximately the same, the gas pressure regulator may

be adjusted as follows:.

To increase input. Remove regulator sealing cap

and turn gas pressure regulator adjusting screw

clockwise.

To decrease input. Remove regulator sealing cap and

turn gas pressure adjusting screw counterclockwise.

Checking Propane Gas Input

The burner orifices are sized for rated input with a

manifold pressure of 11.0” w.c. for propane gas. Con­

nect a manometer of the 1/8” pressure tap on the

chiller manifold gas valve. With the burners fired, ad­

just regulator at the supply tank to provide a pressure

of 11.0” w.c. Check manifold pressure of each chiller.

Cheek the furnace manifold pressure to see that it is

also 11.0 inches w.c.

Burner Adjustment

To adjust the primary air to each burner, partially

close the air shutter until there is a slight yellow tip at

the top of each ñame, then open the air shutter until

the yellow tip just disappears. This should be done af­

ter the burners have been operating at full input for 5

minutes.

VIII. FURNACE OPERATION

In order to check the furnace for proper performance,

the following sequence of control operation is given.

CAUTION: The pilot valve and main burner manual

valve must be closed for at least five minutes before

starting the furnace.

1. Set the thermostat system switch to “heat”, set the

fan switch to “auto” and set the thermostat below

room temperature.

2. Turn on electricah power to the unit.

3. Open pilot gas valve. Gas will flow to the pressure

switch and to the pilot. The electrical contacts in the

pressure switch close, energizing the reignition coil

which ignites the pilot gas. (Natural gas only; pilots

on propane unit must be lighted manually per instruc­

tion on rating plate.)

The pilot flame causes the monometal contacts in the

Bryant 733 pilot to “Break” the re-ignition coil circuit

-

7

-

This manual is related to the following products: