beautypg.com

Figure 2—dimensional drawing, Table i, Heating ratings and capacities 180/240-479 – Bryant 479 D User Manual

Page 2: Table ii, Cooling ratings and capacities

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

.THERMOMETER WELL (4)

15

Í16

22|^

fil­

lio

V M.RT GAS
CONNECTION

28

á

f4-

-76-^

f

/3;

18-^

SIZE A

B

C

D

180 175 68 39-1/8

16-15/16

240 195 88 39-13/16 21-1/32

Approximate Shipping Weights

180-479..................................... 4900 lbs.

240-479.............. .......................5700 lbs,

-B-

®16

66^

ERT. DRAIN CONNECTION

Figure 2—Dimensional Drawing

TABLE I

HEATING RATINGS and CAPACITIES 180/240-479

Input 1st stage

Btuh

225,000

Output 1st Stage

Btuh

168,000

Input 1st and 2nd Stage

Btuh

450,000

Output 1st and 2nd Stage

Btuh

337,000

Approved Temp Rise

Model 180-479

°F

45 - 75

Model 240-479

°F

20 - 50

TABLE II

COOLING RATINGS and CAPACITIES

MODEL

180-479

240-479

Capacity (Total Cooling)

Btuh

180,000

240,000

Air Flow

CFM

6,000

8,000

External Static Pressure

In. wg.

0.3

0.4

Entering Air Temperature

°F

80/67

80/67

Entering Water Temperature

°F

45

45

Gas Input (Total)

Btuh

450,000

600,000

Electrical Input (Total)

KW

5.0

6.0

Refrigerant

Type

R717

R717

Amount per Chiller

Lbs.

18

26

Total Solution per Chiller

Lbs.

55

79