beautypg.com

X. maintenance, Lubrication – Bryant 479 D User Manual

Page 10

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

The ambistat switch contacts will close again when

the chilled water supply temperature rises to 42°F.

The energized gas valve turns the gas on again.

X. MAINTENANCE

Cleaning the Heating Unit.

1. Be sure that the main line disconnect switch is in

the OFF position.

TAG SWITCH WITH A SUITABLE WARNING

LABEL.

2. Remove the front access panel.

3. Turn off the manual gas valve and the pilot valve.

4. Disconnect the pilot and escapement tubing.

5. Remove the burners.

6. Remove the flue baffle retainer and the flue baf­

fles.

7. Clean the flue passages with a suitable brush.

8. Reassemble the furnace by reversing the above

procedure, making sure all seals are reinstalled

properly.

9. Check belt conditions and proper tension of belt

(approximately 1/2 inch deflection).

10. Filters in the 180-479 are of the disposable type

and should be inspected periodically and replaced

when dirty with filters of the same type and size.

Filters in the 240-479 are permanent type filters and

should be cleaned periodically. Make sure the arrows

on the edge of the filter point in the direction of the

airflow.

Lubrication

Some blower motors are equipped with permanent

lubricated bearings and require no further

lubrication.

Blower motors that require lubrication are equipped

with oil cups. Oil motor bearings with SAE 10-20 non­

detergent oil each heating and cooling season.

NOTE: BLOWER BEARINGS ARE OF THE PER­

MANENT LUBRICATED TYPE AND DO NOT

REQUIRE ANY FURTHER OILING.

Cleaning the Condenser Coil

The condenser coil fin surfaces should be inspected

from time to time and cleaned as necessary. Cleaning

may be accomplished by washing the fins with low

pressure water from a garden hose. Detergent may be

used, prior to rinsing, when oil or grease has coated

the fin surfaces. Care must be taken to be sure that

the soft aluminum fins are not bent.

WARNING: Disconnect the electric power before

cleaning the cooling coil.

Summer Chiller Operation

It may be necessary to drain, flush and refill the

chilled water system of each chiller with tap water if

antifreeze was used for winter protection. A high an­

tifreeze concentration will result in a reduction of the

cooling capacity of the unit.

Be sure to add one package of Chilled Water Additive

P/N 62875D1 to the chiller tank of each chiller of

Model 180-479 or the Model 240-479 when water only

is used in the chilled water system for summer

operation.

-