beautypg.com

Purging gas lines, V. electrical connections – Bryant 479 D User Manual

Page 4

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

DRIP LEG
WITHIN'STRUCTURE

Figure 4—Drip Leg Location

5. The joint compound (pipe dope) used must be

resistant to the action of propane gas.

6. Support all piping with appropriate hangers. Use a

minimum of one hanger every ten feet.

7. After all gas connections are made, check for

leakage using soap and water solution, or leak-check

unit in accordance with local utility regulations.

WARNING: NEVER USE A MATCH OR OPEN

FLAME FOR LEAK TESTING.

specifications. Electrical connections must be made in

accordance with the National Electrical Code and the

electrical code of the local area.

The field high voltage connections are made to the

disconnect box located between the two chillers at the

right end of the unit.

The field low voltage wiring consists of running seven

wires from the thermostat subbase to the low voltage

terminal block in the furnace. See Figure 5 for low

voltage field wiring.

Purging Gas Lines

After making all gas connections and checking for

leaks, it is now necessary to purge the supply lines to

eliminate trapped air.

Thermostat P/N 34427D55

and

Subhase P/N 34427D59

WARNING: NEVER PURGE GAS LINES INTO

THE COMBUSTION CHAMBERS OF THE FUR­

NACE OR CHILLERS.

1. With the furnace manual gas valve and pilot

shutoff valve closed, disconnect the pilot supply tube

at the pilot shutoff valve on the furnace.

2. Open the manual shutoff valve; then open the pilot

shutoff valve and allow the supply line to purge until

the odor of gas is detected. Immediately upon detec­

ting a gas odor, turn off the gas and reconnect the

pilot supply tube. Allow at least five minutes to elapse

before lighting pilot.

3. Purge the gas line to each chiller in the same man­

ner as described for the furnace.

V. ELECTRICAL CONNECTIONS

The Model 479 requires a 3 wire, 230 volt, 60 cycle, 3

phase power supply. Check the unit rating plate to

make sure the power supply meets all the electrical

-

4

-