Installation Instructions

479

Sizes 180 & 240

Series E

ATTACH TO INSTALLATION INSTRUCTIONS 39479D8

I

39479D12
4/1/72

Use attached 39479D8 Installation Instructions (with changes indicated below) to in­

stall sizes 180 and 240 of Model 479, Series E, units.

Models 180- and 240-479 Series E units differ from Series D units as described below.

1. GAS INPUT to the cooling section of Model 180-479 was Increased from 450,000 Btuh

to 492,000 Etuh C.246,000 Btuh input each chiller). The generator burner orifices

were changed from #39 drill size to #36 drill size on the natural gas unit. The

burner orifices on the propane unit were changed from #53 drill size to #52 drill

size.

2. GAS INPUT to the cooling section of Model 240-479 was increased from 600,000 Btuh

to 640,000 Btuh C320,000 Btuh input each chiller). The generator burner orifices

were changed from #41 drill size to #39 drill size'on the natural gas unit. The

burner orifices on the propane unit were changed from #54 drill size to #53 drill

size.

3.

4.

AUTOMATIC PILOT REIGNITION is used on both natural and propane units in both the
heating and cooling sections on both Models 180- and 240-479. The wiring diagrams

on pages 11 and 12 apply to both natural and propane gas units.

FUSE SIZE was changed on Model 180-479.

30 amp fuses.

The 180-479 now uses one 60 amp and two

NOTE: Hydraulic Pump Heater Kit P/N 65134D01 (2 required) must be field installed on

each chiller if the cooling section is to be operated at outdoor temperatures below
40°F. Adding the heater kits permits operation of the cooling section at outdoor temp­

eratures down to -30°F. Antifreeze must also be added for protection at the lowest

outdoor temperature.