■ À

To install this system you will need:

1 — 619C fan coil

1 — 700C or 705C outdoor unit

1 — Remote controller kit (included with 619C fan coil) —

note that kit normally includes 15-ft long wire cable;

however, cable length up to 200 ft can be ordered.

1 — Low Ambient Kit (if required for your application)

1 — Check-Flo-Rater™ Metering Device Kit (included with

619C fan coil)

1 — Fresh-Air Intake Kit (if required for your application)

1 — Condensate Pump Kit (if required for your application)

NOTE:

Refrigerant pipe, drain pipe, wire, etc., are also re­

quired to install system.

Be sure you have the required parts before beginning instal­

lation. The 619C unit utilizes a microprocessor control sys­

tem to deliver optimal levels of comfort and efficiency. Be sure

to follow these instructions carefully to obtain proper func­

tioning of the unit.

B. Inspecf^hipmeiit

Upon receipt of shipment check unit for damage. Forward claim

papers directly to the transportation company. Manufac­

turer is not responsible for damage incurred in transit.

Check all items; if any item is missing notify your distribu­

tor. To prevent loss or damage, leave all parts in original pack­

ages until installation.

C. Before Installation

Perform the following steps before installing indoor unit

(Fig. 2). Place the unit upside down on the floor, then:

1. Remove side panels by sliding forward, then away from

sides of unit.

2. Remove air filters from inlet grilles; then remove and

retain screws securing inlet grilles to indoor unit.

3. Remove inlet grilles from indoor unit by sliding

forward.

Table 2 - Application Range

COOLING

Maximum

Minimum

Indoor

Outdoor

Indoor

Outdoor

95 F DB

71 F WB

125 F DB

67 F DB

57 F WB

55 F DB*

HEATING

Maximum

Minimum

Indoor

Outdoor

Indoor

Outdoor

80 F DB

71 F WB

75 F DB

65 F WB

55 F DB

-20 F DB

LEGEND

DB — Dry Bulb
WB - Wet Bulb

'Unit may be equipped with a iow-ambient control that will allow

operation down to ~20 F

I. COMPLETE PRE-INSTALLATION CHECKS

A. Unpack Unit

Store unit in the original packaging until it is moved to the

final site for installation. When removing unit from carton,

lift unit by its 4 corners; DO NOT lift unit by its plastic parts.

LOOSEN eOLTS

AND

SLIDE-

MOUNTING

BRACKET

THIS

DIRECTION—TO REMOVE

2 T/8

tSSJ

DISCHARGE AIR

SLIDE SIDE PANEL THIS

OIRECTION—TO REMOVE

PIPING JOINT

(LIQUID SIDE)

PIPING JOINT

(VAPOR SIDE)

REMOVABLE AIR FILTER

PIPING

KNOCKOUT

(RIGHT SIDE)

[INLET AIR

'-DRAIN CONNECTION

NOTE: Dimensions shown in brackets [ ] are in mm

Fig. 2 — Removal of Mounting Brackets

from Indoor Unit

Table 3 — Physical Data

UNIT 619C

NX0240E0

NX0360E0

NX0480E0

NX0240W0

NX0360W0

NX0480W0

OPERATING WT (lb)

108

117

140

110

119

142

REFRIGERANT

R-22, Check-Flo-Rater Control

FAN

Rpm

High

1035

1310

1345

1035

1310

1345

Med

990

1160

1307

990

1160

1307

Low

940

1010

1270

940

1010

1270

Nominal Cfm (High Speed)

635

935

1300

635

935

1300

COIL

Rows

4

4

4

4

4

4

Face Area (sq ft)

2.189

2.625

3 069

2 189

2.625

3.069

FIns/in.

149

149

14.9

14.9

14.9

14.9

Number of Circuits

4

4

8

4

4

8

CONNECTIONS

Suction (in.) Flare

%

3/4

3/4

3/a

3/4

3/4

Liquid (in.) Flare

%

3/a

3/a

3/a

Ve

3/a

Condensate Drain (in.)

%

3/4

3/4

3/4

3/4

3/4

LINE SIZES

Suction (in.)

%

3/4

%

Va

3/4

%

Liquid (in.)

%

%

%

3/e

3/a

3/a

Condensate Drain

3/4

3/4

3/4

3/4

3/4

3/4

-