beautypg.com

Bryant PAYNE 619C User Manual

Page 14

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

1

SERVICE

NOTE:

Refer to the control, service and troubleshooting guide

sections of the duct-free systems manual for a complete de­

scription of the control system and for detailed service and

troubleshooting procedures. This manual is available from your

distributor.

TROUBLESHOOTING

I. DIAGNOSTIC CODES

This unit is equipped with a microprocessor control which con­

tinuously monitors the operation of the unit. If an opera­

tional fault is detected, a fault code appears on the LCD dis­

play of the remote controller. A red LED indicator light, located

on the control board in the control box of the indoor unit, will

emit a flash code which can be used to troubleshoot a system

problem. The control will continue to monitor the unit and, if

thè conditions which cause the fault are cleared, the unit will

return to normal operation. If the fault code is present for 5

cycles of the unit, the unit will be locked out and the alarm

code will be displayed alternately with the temperature on

the remote controller LCD display.

If the LED indicator light continuously flashes on for one sec­

ond, then off for one second, the control is functioning prop­

erly and no fault is present. A fast flashing LED indicates

that a fault has been detected. Table 7 lists the number of

quick flashes and the associated fault. If the system does not

operate, the remote controller does not display a fault code,

and the LED indicator does not flash, either the power to the

control board is off, or the control board has failed.

Table 7 — System Fault Codes

FAULT
CODE*

NO. OF

FLASHES

SYSTEM FAULT

E2

2

Outdoor Coll Thermistor

E3

3

Outdoor Air Thermistort

E4

4

Room Air Thermistor

E5

5

Indoor Coil Thermistor

E6

6

Discharge Air Thermistor

E7

7

Compressor Malfunction

E8

8

Reversing Valve Malfunctlonf

E11

11

Electric Heat Malfunction

E12

12

Outdoor Coil Temperature

‘The fault code is alternately displayed with the temperature on the re­

mote controller LCD display

tHeat pump systems only

II. TEST MODES

The remote controller allows troubleshooting of the system

by running a series of test modes. These tests may be man­

ually initiated with the remote controller to test the system

operation:

• Fan Only Test

• Cooling Mode Test

• Dehumidification Test

• Heat Pump Heating Test

• Emergency Heat Test

See separate controls, service, and troubleshooting guide for

additional details on operating test modes.

III. SYSTEM TESTS

System tests listed below are performed continuously by the

microprocessor. If a fault is indicated, then the system al­

lows only limited operation until the problem is resolved. If

the problem resolves itself, then the code is cleared and op­

eration resumes.

A. Indoor Coil High-Temperature Protection (Heat Pump Sys­
tems Only)

If indoor coil temperature is greater than or equal to 145 F

but less than 165 F for one minute or more, the system shuts

down.

B. Outdoor Coil High-Temperature Protection (Cooling or
Dehumidification Mode Only)

If outdoor coil temperature is greater than or equal to 145 F

but less than 165 F for one minute or more, the system shuts

down.

C. Indoor Coil Freeze Protection (Cooling or Dehumidifica­
tion Mode Only)

If indoor coil temperature is less than or equal to 28 F but

more than —13 F for 4 minutes and the compressor has run

for 24 continuous minutes, the system shuts down.

D. Thermistor Tests

Each thermistor is tested for high limit out of range (shorted

condition) and low limit out of range (open condition). If the

thermistor is out of range, the fault status indicator comes

on and the LED flashes the appropriate fault code.

E. Compressor Failure

If the System is in COOLING or DEHUMIDIFICATION Mode

After 2 minutes of operation, if the temperature of the in­

door coil is not 2° F less than at the time the call for cool­

ing started, then a compressor failure is indicated on the re­

mote controller LCD display.

If the System is in HEAT PUMP HEATING Mode - After 2

minutes of operation, if the temperature indicated by the out­

door thermistor is not 2° F less than at the time the call for

heating started, then a compressor failure is indicated.

F. Reversing Valve Failure

If the System is in COOLING or DEHUMIDIFICATION Mode

After 4 minutes of operation, if the temperature at the in­

door coil is 2° F more than at the time the call for heating

started, then a reversing valve failure is indicated.

If the System is in HEAT PUMP HEATING Mode — After 4

minutes of operation, if the temperature indicated by tbe in­

door coil is not 2° F less than at the time the call for heat­

ing started, then a reversing valve failure is indicated.

G. Electric Heater Failure

If, 4 minutes after the heater is energized, the discharge-air

temperature is not 2° F above the return-air temperature, an

electric heater failure is indicated.

H. Filter Dirty Indicator

Indicator (on remote controller LCD display) turns on after

250 hours of indoor fan operation.

-

14

-