beautypg.com

Size 048, 208v- or 230v-60-3 – Bryant 559B User Manual

Page 5

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

justed for proper airflow.

Recommended evaporator airflow is 350 to 450 CFM per

12,000 Btuh.

1. Set thermostat to call for cooling, thus energizing unit.

2. Measure static pressure in duct system at unit.

3. To determine airflow across evaporator coil, see Tables

III through VII.

Model 559B utilizes a direct-drive blower, factory-wired on

high-speed tap. If airflow is incorrect, blower speed can be

adjusted as follows:

1. Disconnect electric power to unit.

2. Disconnect cooling relay lead from high-speed tap

(black wire). Tape end of wire removed.

3. Refer to appropriate Air Delivery Performance Table

and connect relay lead to correct speed tap.

Blue wire med speed

Orange wire med-low speed

Red Wire low speed

4. Recheck system static pressure.

The air conditioner has been tested and factory sealed.

There is no need to check refrigerant charge. If it is

necessary to open refrigerant circuit, contact your Bryant

Distributor for proper procedure. The type and amount of

refrigerant are listed on rating plate.

Typical Sequence of Operation

Do not leave installation until unit has been observed

throughout one or two complete cycles. Installer, should

make certain during this time that all components are

operating in correct sequence. Refer to line-to-line wiring

diagrams. Figure 10 or 11. The following sequence of

operation pertains to the units shown; however, the

sequence of operation of all units is very similar.

NOTE: Although the unit wiring may vary slightly from

that shown in Figure 10 or 11, the sequence of operation

will not be affected.

Sizes 024, 030, and 036, 230V-60-1

Line voltage is supplied through terminals LI and L2 to

compressor contactor (2D) and to primary of control trans­

former (lAl). An external low-voltage thermostat is con­

nected across low-voltage wires R, Y, and G.

Set system switch to COOL and fan switch to AUTO on

thermostat. On call for cooling, power is supplied from con­

trol transformer (lAl) through wire R, external thermostat,

wire Y, low-pressure switch (7C), and contactor holding coil

(2D) to other side of control transformer (lAl), closing con­

tactor contacts (2D).

When contactor contacts (2D) close, condenser fan motor

(3C) is energized through run capacitor (4A2), starting con­

denser fan. In addition, power flows through compressor

motor run capacitor (4A3), compressor start capacitor

(4Cl), start relay (2K), and compressor motor (3J), starting

compressor motor.
When cooling fan relay contacts (2A) close, power flows

through run capacitor (4A1) and blower motor (3D1)

starting blower motor.
When thermostat ceases to require cooling, it breaks circuit

between wires R and Y and wires R and G, shutting down

unit.

Size 048, 208V- or 230V-60-3

Line voltage is supplied through terminals Ll, L2, and L3

to compressor contactors (2D) and to control transformer

(lAl). An external low-voltage thermostat is connected

across low-voltage wires R, Y, and G. Set system to COOL

and fan switch to AUTO on thermostat.

On a demand for cooling by the external thermostat, power

is supplied from control transformer (lAl) through ter­

minal R. Terminal R makes to terminals Y and G through

the thermostat.

As R makes to G, the coil of the cooling fan relay (2A1) is

energized, closing the fan relay contacts (2A1). Power is

now allowed to flow through blower motor run capacitor

(4A1), and the blower motor (3D1) starts.

As terminal R makes to terminal Y through the thermostat,

the coil of cooling relay (2A2) is energized, closing the

cooling relay contacts (2A2). Power is now allowed to flow

through the low-pressure switch (7C), the compressor in­

ternal thermostat (7H), compressor overload contacts (8A),

and the Bryant COMPROTEC'" circuit which includès

timer motor (3M), and the coil of the holding relay (2C).

The energized coil of the holding relay (2C) closes its nor­

mally open contacts and opens its normally closed contacts.

Timer motor (3M) runs through a 15-second (approx.) cy­

cle. The timer motor contacts are then switched. Power is

now allowed to flow through the coil of compressor con­

tactor (2D), which closes the normally open contacts of

compressor contactor (2D).

When compressor contactor contacts (2D) are closed, power

is allowed to flow through compressor overloads (8A) and

compressor motor (3L) starts. At this same time, power is

allowed to flow through low-ambient condenser fan switch

(7K), condenser fan run capacitor (4A2), and the two-speed

condenser fan motor (3D2) starts. When outdoor tem­

perature drops to 85°F, low-ambient condenser fan switch

(7K) will switch contacts, energizing a lower speed of con­

denser fan motor (3D2).

When the demand for cooling is satisfied, the external ther­

mostat breaks the circuit between terminal R and terminals

Y and G. Breaking this circuit deenergizes compressor

holding coil (2D), cooling relay coil (2A2), and cooling fan

relay coil (2A1). The condenser fan motor (3D2), com­

pressor motor (3L), and blower motor (3D1) are now

deenergized.
At the same time, the holding relay coil (2C) is deenergized,

opening its normally open contacts and closing its normally

closed contacts. Power now flows through normally closed

contacts of holding relay (2C) and timer motor (3M). In ap­

proximately 4 minutes 45 seconds, the timer motor contacts

switch, breaking circuit to timer motor. The unit is now in a

“standby” position, ready for the next demand for cooling

by the external thermostat.

-

5

-