Input Adjustment

1. Turn off all other gas appliances on same meter.

2. Set thermostat high enough to ignite burners.

3. Check cu ft of gas burned per minute. Multiply

value by 60 minutes to determine input (in

thousands of Btuh). Rating should be within

5% of nameplate input rating.

4. To adjust input, remove combination gas valve

cap covering regulator adjusting screw. (See
Fig. 7.)

5. With a small screwdriver, rotate adjustment

screw clockwise to increase or counterclockwise
to decrease pressure. Do not change pressure
more than ± 0.3 in. wg.

6. Replace regulator adjustment screw cap.

IMPORTANT; Refer to operating and main-
tenance instruction Eterature to ensure better,
longer, and more reEable service from your new
Carrier furnace.

TROUBLESHOOTING

Burner Will Not Operate

POWER FAILURE — Power switch off — set to
on, blown fuse — replace, defective wiring —
replace

NO POWER TO CONTROLS - Thermostat set too
low, dirty or defective — reset, clean or replace as

applicable; defective transformer — replace; faulty

limit switch — replace; blown fusestat ~ replace

BURNER WILL NOT IGNITE ^ Low gas pressure
or no gas to unit — check if manual shutoff valve is
closed, check gas supply, check for clogged gas line

and clean or repair, adjust gas pressure with all
appliances operating; faulty thermocouple — check

with millivoltmeter and replace if necessary; pilot

light extinguished — locate cause and relight, dirty
pilot — clean

Burner Operates, But Heating Inadequate

UNIT UNDERSIZED — Size selected incorrectly —

never overfire, replace with properly sized unit

FUEL INPUT TOO LOW — Wrong orifice size —

replace orifice; regulator set too low — readjust.

THERMOSTAT OPENS TOO SOON - Wrong
anticipator setting ~ readjust; thermostat out of

cahbration — recalibrate; thermostat set wrong —

check and reset as necessary; wrong thermostat
location — relocate.

LIMIT SWITCH CYCLES BURNER - Dirty filters
-- clean or replace, faulty fan switch or motor —

repair or replace; blower speed too low — readjust;

fan switch set too high — readjust; duct system

restricted — remove restriction.

Poor Combustion and Flame Characteristics

SMOKY FLAME — Insufficient air — adjust air

inlet; flue restriction — remove restriction; down-

draft — eliminate downdraft using flue caps on
vents
NOISY BURNER — Too much air — adjust air

inlet, incorrect input — make correction as
required