beautypg.com

Start-up, Preliminary checks, A caution – Carrier 38HD User Manual

Page 7

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

Table 3 — Electrical Data (60 Hz)

OUTDOOR

UNIT 38HD

V/PH

OPER VOLTS*

COMPR

FAN

FLA

MCA

MAX FUSE

OR HACR TYPE
CKT BKR AMPS

Max

Min

LRA

RLA

018
024
030

036
048
060

208/230-1

254

187

52 0
60.0
65 0
82 0

127 0
135 0

84

10.6
13.5
165
25 0

30.7

.70

70
70

1 45
1 45
1.45

120
140
180
22 0
33 0

40 0

15
20
30
35
50
60

036

67 5

10.0

1 45

140

20

048

208/230-3

254

187

98 5

15 4

1.45

21 0

35

060

105.0

19.6

1.45

26 0

45

036

33 8

50

80

70

15

048

460-3

506

414

49 3

77

80

11 0

15

060

55 0

104

.80

14.0

20

FLA — Full Load Amps
HACR — Heating, Air Conditioning, Refrigeration
LRA — Locked Rotor Amps

MCA — Minimum Circuit Amps per NEC Section 430-24

RLA — Rated Load Amps (compressor)

‘Permissible limits of the voitage range at which unit wiil operate

satisfactorily

NOTE; Control circuit is 24v on all units and requires external
power source

Example: Supply voltage is 460-3-60.

ABC

AB

=

452

volts

BC = 464 volts
AC = 455 volts

Average Voltage =

452 + 464 + 455

1371

457

Determine maximum deviation from average voltage

(AB) 457 - 452 = 5 volts
(BC) 464 - 457 = 7 volts
(AC) 457 - 455 = 2 volts

Maximum deviation is 7 volts.

Determine % voltage imbalance:

% Voltage Imbalance = 100 x

457

1.53%

This amount of phase imbalance is satisfactory as it is

below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase im­
balance is more than 2% contact your local electric

utility company immediately.

Unit failure as a result of operation on improper line

voltage or excessive phase imbalance constitutes abuse
and may cause damage to electrical components. Such
operation

would

invalidate

any

applicable

Carrier

warranty.

START-UP

Preliminary Checks

1 Check that all internal wiring connections are tight

and that all barriers, covers and panels are in place.

2. Field electrical power source must agree with unit

nameplate rating

3 All service valves must be open.

4. Crankcase heater must be tight on compressor

crankcase.

Leak Test field piping and fan coil by pressure method

described

in

Carrier

Standard

Service

Techniques

Manual, Chapter 1, Section 1-6. Use R-22 at approxi­

mately 25 psig backed up with an inert gas to a total
pressure not to exceed 245 psig.

Before starting unit, crankcase heater must he on for

24 hours to he sure all refrigerant is out of the oil. To

energize crankcase heater, proceed as follows: set space
thermostat above ambient so there will be no demand for
cooling. Close field disconnect. The crankcase heater

is now energized.

Evacuate and Dehydrate field piping and fan coil
by either of the methods described in Carrier Standard
Service Techniques Manual, Chapter 1, Section 1-7.

A CAUTION

Service valves must be fully backseated to close
service port. There is no Schrader valve at the service
port and failure to backseat the valve could result in
loss of system charge or personal injury.