beautypg.com

Fig. 6 — typical control circuit connections, A warning – Carrier 38HD User Manual

Page 6

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

________I

ARRANGEMENT A-(COOLING ONLY)

ARRANGEMENT B-ONE TRANSFORMER

(COOLING AND ONE-STAGE HEATING)

ARRANGEMENT C-ONE TRANSFORMER

(COOLING AND TWO-STAGE HEATING)

*IFR and IFM are located in furnace on heating-cooling applica­

tions If accessory IFR is required for cooling-only applications,

locate (IFR) in fan coil

C

HC

-

IFM

IFR

Trans —

Contactor (12-va)
Heating Control

Indoor Fan Motor
Indoor Fan Relay

Transformer

____ —. Field Wiring

- Factory Wiring

NOTE Refer to unit wiring label for wire colors C t o G a n d C t o Y
connections

f

Fig. 6 — Typical Control Circuit Connections

CONTROL CIRCUIT WIRING — Control voltage is
24 volts (40 va minimum). See Fig. 6 and unit label
diagram for field-supplied wiring details. Route control

wires through opening in unit side panel to connection in
unit control box.

TB — Terminal Board

— O

------ TB Connections

Field Wiring

Factory Wiring

NOTE; For wire runs up to 50 ft, use no. 18 AWG insu­
lated wire (35 C minimum). For 50 to 75 ft, use no. 16
AWG insulated wire (35 C minimum). For over 75 ft, use

14 AWG insulated wire (35 C minimum).

NOTE: Operation of unit on improper line voltage con­
stitutes abuse and could affect Carrier warranty See
Table 3. Do not install unit in system where voltage may
fluctuate above or below permissible limits.

See Table 3 for recommended fuse sizes. When making

electrical connections, provide clearance at unit for refrig­
erant piping connections

Use furnace oi fan coil transformer as 24-v (40-va

minimum) supply for system as shown in Fig. 7 or use
accessory transformer.

A

WARNING

To avoid personal injury, be sure indoor blower has

stopped before attempting service or maintenance.

Operating voltage to compressor must be within

voltage range indicated on unit nameplate. On 3-phase
units voltages between phases must be balanced within
2% U se the following formula to determine the % voltage
imbalance.

% Voltage Imbalance

max voltage deviation frqm average voltage

Fig. 7 — Line Power Connections

100

X

average voltage