Table 2 — electrical data – Carrier 50DF034 User Manual
Page 8
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Table 2 — Electrical Data
NOMINAL
VOLTS/PH/HZ
VOLTAGE
RANGE
COMPR
NO. 1
COMPR
NO. 2
OUTDOOR
FAN MTR
INDOOR
FAN MTR
EXHAUST
FAN MTR
HEATERS
POWER SUPPLY*
Circuit 1
Circuit 2
Min
Max
RLA
LRA
RLA
LRA
Oly
FLA
Hp
FLA
Hp
FLA
kW
FLA
MCA
MOCP
MCA
MOCP
15
46 0
_
_
_
_
212
250
_
—
15
46 0
3
11
—
—
223
250
—
—
208-230/3/60
187
254
63 5
266
63 5
266
3
7 6
(ea)
15
15
46 0
46 0
3
11
45-54 9
45-54 9
125-138
125-138
214-230
223-230
300-300
300-300
—
—
15
46 0
—
—
75-91 5
208-230
212-212
250-250
156-173
175-200
15
46 0
3
11
75-91 5
208-230
223-223
250-250
156-173
175-200
15
21 0
_
_
_
_
93
110
15
21 0
3
4 8
—
—
98
125
—
—
460/3/60
414
508
27 5
120
27 5
120
3
3 3
(ea)
15
15
21 0
21 0
3
4 8
54 9
54 9
69
69
113
113
150
150
—
—
15
21 0
—
—
91 5
115
170
175
__
__
15
21.0
3
4.8
91.5
115
170
175
—
—
575/3/60
518
660
22
96
22
96
3
2 7
(ea)
15
15
-
3
3 9
—
-
75
79
90
100
-
—
Compr — Compressor
FLA
— Full Load Amps
Hp
— Nominal Horsepower
kW
— Kilowatts
LRA
— Locked Rotor Amps
MCA — Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
RLA — Rated Load Amps
*Fuse only
NOTES:
1 All outdoor fan motors are single-phase motors
2 All heaters are 3-phase assemblies
3 Circuit no. 2 is provided as indicated; total unit MCA is the sum of circuit
no 1 MCA and circuit no 2 MCA
4
Unbalanced 3-Phase Supply Voltage— Never operate a motor where a
phase imbalance in supply voltage is greater than 2% Use the following
formula to determine the % voltage unbalance
% Voltage Imbalance
max voltage deviation from average voltage
= 100 X ■
Example: Supply voltage is 460-3-60
AB = 452 volts
BC = 464 volts
AC = 455 volts
Average Voltage
452 + 464 + 455
1371
3
3
457
average voltage
Determine maximum deviation from average voltage:
(AB) 457 - 452 = 5 volts
(BC) 464 - 457 = 7 volts
(AC) 457 - 455 = 2 volts
Maximum deviation is 7 volts
Determine % voltage imbalance:
% Voltage Imbalance = 100 x= 1 53%
This amount of phase imbalance is satisfactory as it is below the maxi
mum allowable 2%