beautypg.com

Carrier 50DF034 User Manual

Installation, start-up and service instructions

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

HEATING & COOLING

50DF034

Single-Package Cooling Units

Installation, Start-Up and

Service Instructions

SAFETY CONSIDERATIONS

Installation and servicing of air conditioning

equipment can be hazardous due to system pressure and
electrical components. Only trained and qualified service

personnel should install, repair or service air conditioning

equipment.

Untrained personnel can perform basic maintenance

functions of cleaning coils and filters and replacing filters.

All other operations should be performed by trained

service personnel. When working on air conditioning

equipment, observe precautions in the literature, tags and

labels attached to the unit and other safety precautions

that may apply.

Follow all safety codes. Wear safety glasses and work

gloves. Use quenching cloth for unbrazing operations.

Have fire extinguisher available for all brazing

operations.

A

WARNING

Before performing service or maintenance operations
on unit, turn off main power switch to unit. Elec­

trical shock could cause personal injury.

INSTALLATION

Rigging and Unit Placement — Inspect unit for

transportation damage. File claim with transportation

agency. Do not remove shipping skid until unit is ready

to be set in final location. Do not drop unit; keep upright.

Use spreader bars over unit to prevent sling or cable

damage. Rollers may be used to move unit across a roof.

Level by using unit frame as reference. See Fig. 1 for
additional information. Unit weight is shown in Table 1.

Units are designed to be hoisted only. However, units

with optional shipping skids may be moved with a fork

truck. Refer to Accessory Roof Curb Installation Instruc­
tions for additional information as required.

Roof Curb — Assemble and install as described in

instructions shipped with this accessory. Accessory roof
curb and information required to field fabricate a roof
curb of 2-in.

X

14-in. planks is shown in Fig. 2. Install

insulation, cant strips, roofing and flashing as required.

For unit drains to function properly, curb must be level

or within tolerances shown in Fig. 3.

Roof Mount — Check building codes for weight dis­

tribution requirements Unit weight is shown in Table 1.

Slab Mount — Provide a level concrete slab that

extends beyond unit cabinet at least 6 inches. Make a slab
8 in. thick with 4 in. above grade. Use gravel apron in
front of condenser air inlet to prevent grass and foliage
from obstructing airflow.

Alternate Unit Support Methods — Where the

preferred curb or slab mount cannot be used, support
unit with sleepers on perimeter, using curb support area.

However, if sleepers cannot be used, support long sides

of unit (dimension A, Fig. 4) with three 4-in. x 4-in. pads

equally spaced. U nit may sag if supported by corners only.

Positioning — Unit condenser air inlets and outlets

may be located in any compass direction since they are

not affected by wind. Provide clearances around and
above unit for airflow, safety and service access (Fig 4).

Do not install unit in an indoor location Do not locate

air inlets near exhaust vents or other sources of con­
taminated air

Although unit is weatherproof, guard against water

from higher level runoff and overhangs.

NOTES-
1 All unit panels must be In place when rigging.

2 Do not handle unit with fork trucks
3 Use 4 cables and four 2-by-4’s or 4-by-4's of dimensions

shown.

Fig. 1 — Rigging Details

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obiigations.

Book|l

PC111

Catalog No 565-032

PrintedinUSA

Form 50DF-9SI

Pgl

4-86

Replaces: 50DF-7SI

For replacement items use Carrier Specified Parts

Tab lib