beautypg.com

Carrier 50DF034 User Manual

Page 12

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

above enthalpy set point, the outdoor air dampers remain
at minimum position.) Economizer acts as the first stage
of cooling, providing “free cooling” with outside air. If
outside air alone cannot satisfy the cooling requirements
of conditioned space, economizer cooling is integrated
with mechanical cooling.

Compressor(s), working simultaneously with econo­

mizer, will come on in stages to meet the cooling load.

As the conditioned space temperature approaches the

thermostat’s cooling set point, stages cycle off, last stage
first. After all stages of mechanical cooling are off, econo­

mizer modulates to minimum position.

During the cooling cycle, a discharge air sensor senses

discharge air temperature. If discharge air temperature

drops below 62 F, economizer starts to modulate toward

minimum position. At 50 F discharge temperature, the

economizer will be at minimum position.

Heating — System switch set at HEAT or AUTO., fan

switch at ON or AUTO., thermostatset at desired setting.

When thermostat calls for heating, one or 2 stages of heat

energize to satisfy heating demand.

As space temperature approaches the heating tem­

perature set point, heating stages cycle off.

During heating, economizer is limited to the minimum

position to provide outdoor air for ventilation

requirements.

OPERATING SEQUENCE WITH ECONOMIZER

AND ENERGY MANAGEMENT ACCESSORY

(using electronic thermostat or transmitter).

Clock in remote control box switches controls to

OCCUPIED mode. Indoor air fan runs continually while

in OCCUPIED mode

If return air temperature is below the adjustable setting

of morning warm-up thermostat, outdoor air dampers
remain closed.

When return air temperature goes above setting of

morning warm-up thermostat, economizer goes to adjust­

able minimum position.

When thermostat calls for cooling and outdoor air

enthalpy is below setting of enthalpy controller, econo­

mizer modulates open. (If outdoor air enthalpy is above
enthalpy set point, economizer remains at minimum
position.) The economizer acts as the first stage of cool­
ing, providing “free cooling” with outside air. If outside
air alone cannot satisfy cooling requirements of the
conditioned space, economizer cooling is integrated with

mechanical cooling.

Compressor(s), working simultaneously with econo­

mizer, will come on in stages to meet the cooling load.

As the conditioned space temperature approaches the

thermostat’s cooling set point, stages cycle off, last stage
first. After all stages of mechanical cooling are off, econo­
mizer modulates to minimum position.

During the cooling cycle, a discharge air sensor senses

discharge air temperature. If discharge air temperature
drops below 62 F, the economizer modulates toward

minimum position. At 50 F discharge temperature, the

economizer will be at minimum position.

At the end of the DAY (OCCUPIED) mode on the

clock, unit controls enter the NIGHT (UNOCCUPIED)

mode Economizer closes. Indoor air fan runs only on a

call for heating or cooling. Temperature controls go into

HEATING SETBACK, COOLING SETUP or COOL­
ING SHUTDOWN mode.

HEATING SETBACK is field selectable at the unit

for 5°, 10°, or 15° below set point on room thermostat.

COOLING SETUP is field selectable at the unit for

5°, 8°, or 12° above set point on room thermostat.

During the UNOCCUPIED mode, unit continues to

use economizer cooling first and then integrates econo­
mizer cooling with mechanical cooling to meet cooling
requirements.

A 5-hour bypass timer is located in the remote control

box to provide air conditioning during normally un­
occupied hours

POWER EXHAUST OPERATION — Units have an
auxiliary switch located on the damper motor. This
switch is factory set to prevent the power exhaust fans
from operating when the economizer damper is less than
30% open.

If other than factory setting is desired, adjust as follows:

NOTE. Adjustment does not require running the motor

1. Motor must be in the fully closed position.

2. Referring to Fig. 16, take off “C” clip and drive

bracket. Remove screws at 4 corners of housing. Pull
off return spring housing.

STARTING POSITION

NOTE POSITION

OF RED DOT

CENTERLINE

ADJUST CAMS

OPERATIONAL

Each adjustment mark repre­

sents 10 degrees of motor ro­

tation Use marks and center

of cam roller as adjustment
guide

Loosen operational cam ad­

justment screw Rotate both

cams clockwise the number
of degrees motor must travel

before switch makes Tighten
screw.

Red dot will be to right of centerline if switch is properly adjusted

Fig. 17 — Adjusting Switch Make and Break Points

12