AIR IN

NOTE: Fan position on motor shaft should be as close to motor as possible without touching.

Figure 2—Dimensional Drawing

TABLE I—DIMENSIONS (In Inches)

Size

----------X---------- ----------C----------

D

----------

1

----------

F

G

H

K

025

27-3/8

24-9/16

6-3/8

1-7/8

3/8

11-9/16

11-3/4

11/32

3/4

040, 047 & 054

27-3/8

30-9/16

6-3/8

1-7/8

3/8

11-9/16

11 -3/4

11/32

3/4

TABLE II—SPECIFICATIONS

Size

025

040

047

054

Refrigerant Type

R-22

R-22

R-22

R-22

Factory Refrigerant Charge

Lbs-oz

4-8

6-8

7-2

6-11

Refrigerant Tube^

Liquid

3/8

3/8

3/8

3/8

Connection Size (Compatible)

Vapor

3/4

3/4

3/4

3/4

Approx Shipping Weight

Lbs

155

200

230

232

♦Refer to appropriate refrigerant tube sizing table to determine correct liquid- and suction-tube diameters.

TABLE III—ELECTRIC CONNECTIONS

Size

025

040

047

054

Nameplate

Volts—Phase (60-Hertz)

230—1—50

400—3—50

400—3—50

400—3—50

400—3—50

Operating Voltage Range

207-253

360-440

360-440

360-440

360-440

Unit Ampacity for Elec­
trical Conductor Sizing.

18.5

6.7

9.2

14.1

15.4

Total Unit Amps

15.1

5.6

7.6

11.5

12.5

Min Branch Circuit
Wire Size

AWG No.

12

14

14

14

12

Copper
Conductor^

Max Length

In Ftt

94

321

236

156

228

Largest Wire Size

Terminal Will

Type Conn

Screw

Screw

Screw

Screw

Lug

, Accommodate

AWG No.

6

6

6

6

6

Max Branch. Circuit
Fuse Sizet

Amps

25

10

15

20

20

NOTE: Use copper wire only between disconnect switch and unit.

♦If other than 75° C copper conductor is used, determine size from unit-ampacity and the National Electric Code. Voltage drop of wire must be less

than 2% of unit rated voltage.

fLength shown is as measured one way along the wire path between the unit and service panel-for minimum 2% voltage drop.
$Sing)e-phase units may use fuses or HACFI-type circuit breakers of same size as noted.