beautypg.com

Checkout list – Carrier 38GP User Manual

Page 10

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

UNTIL ALL REFRIGERANT CONNECTIONS HAVE
BEEN MADE AND BOTH SERVICE VALVES HAVE
B E E N C H E C K E D F O R T H E O P E N P O S I T I O N .
(TURNED COUNTERCLOCKWISE.) IT IS NECESSARY
TO REMOVE THE VALVE STEM CAPS TO CHECK.

The single-phase compressor motor used in this condensing
unit may be a permanent-spht-capacitor-tj^e (PSC) motor,
designed to start under low-load conditions only; therefore,
make sure that the system pressures have equahzed before
attempting to start the unit: this takes approximately 3

minutes. Do not short-cycle the unit with the thermostat or
disconnect, as this will cause the compressor to tripout on
overload. For starting under most load conditions, an
optional starting kit is available from your Distributor.

VII. CHECKING CHARGE

No installation is complete until the operating charge level
of the unit is checked. The level of refrigerant operating
charge will determine how efficiently and economically the

unit wiU operate. An overcharged or undercharged unit wiU
lead to insufficient cooling, high operating costs, and the
possibihty of a compressor failure. To check the refrigerant
charge level, proceed as follows:

1. Remove valve stem caps from both service valves and

check valve stems for open position (counterclockwise).

2. Remove gauge port cap from both service valves and

attach gauge manifold. Purge gauge manifold and
hoses.

3. Start unit and allow it to run until operating conditions

stabihze and pressures level out.

4. Evaluate system performance and refrigerant charge

level by determining following information:

a. Low-side pressure gauge reading.

b. Dry-bulb temperature of inlet air at condenser coil.

c. Wet-bulb temperature of inlet air at evaporator coil.

This may be read at central return-air grille.

d. Liquid- or suction-tube temperature at respective

service valve.

NOTE:

Use an accurate superheat, thermocouple, or

thermistor-type thermometer.

e. Compare these readings to those fisted on Unit

Charging Label located on unit. Add or remove
refrigerant as required.

NOTE:

The suction-tube connection of the compressor must

be as cool as the suction tube, and the compressor base

should be warm.

5. When correct refrigerant charge level is obtained,

remove gauge manifold.

6. Replace valve stem and gauge port caps. (Be sure they

are tight.)

NOTE:

Where applicable, stamp the total number pounds of

refrigerant charge onto the rating plate in the space
provided.

VIII. ADJUSTING CHARGE

If, after checking the operating charge level, the unit is
found to be undercharged or overcharged, refrigerant may
be added or removed through the gauge manifold and the
suction service valve.

To add refrigerant to a unit, proceed as follows:

1. Connect clean, dry cylinder of R-22 to center port con­

nection of gauge manifold. Purge hose and connect
gauge manifold to service valves.

2. With refrigerant cylinder in upright position, open

valve on cylinder and slowly open valve on low-pres­

sure gauge of manifold. Add refrigerant in vapor form

until proper amount has been added.

3. When correct refrigerant charge level is obtained, close

valves on refrigerant cylinder and gauge manifold.

4. Remove gauge manifold from service valves. Replace

valve stem and gauge port caps. (Be sure they are
tight.)

To remove refrigerant from a unit, proceed as follows:

1. Slowly open valve on low-pressure gauge side of mani­

fold and vent refrigerant (slowly) through center port
connection of gauge manifold.

2. When desired amount of refrigerant has been removed

to obtain correct refrigerant charge level, close valve on
low-pressure gauge side of manifold.

3. Remove gauge manifold from both service valves.

Replace both valve stem and gauge port caps. (Be sure
they are tight.)

CHECKOUT LIST

WITH ELECTRIC POWER OFF:

1. Check all electrical wiring (both factory and field) for

completeness and tighten all electrical connections
(contactor, capacitors, relays, etc.).

2. Check condenser fan blade for proper insertion depth in

orifice plate.

3. Check evaporator blower puUey and motor pulley (belt-

drive units only) for proper belt alignment and tight­
ness. (Should have 1 in. of sag with normeil finger

pressure.)

4. Tighten all setscrews (evaporator blower, blower pul­

ley, motor sheave, and condenser fan blade).

5. Check condenser airflow for obstructions.
6. Clean or replace air filters. Do not operate system with­

out air filters in place.

7. Leak-test all refrigerant connections (fittings, joints,

gaskets, flanges, etc.)—both factory and field—with a
halide torch or electronic leak detector.

8. Replace all caps on service valves. Be sure they are

tight.

9. Check to be sure all tools and loose parts have been

removed from unit.

10. Check to be sure all panels, covers, and screws are in

place.

11. Following initial inspection, start unit and:

a. Check condenser fan and evaporator blower for

proper rotation.

b. Adjust furnace or evaporator blower for proper air­

flow (approximately 400 cfm/ton).

c. Check fine and low voltage. (Should be within oper­

ating voltage range stamped on unit rating plate.)

d. Check unit for proper operating refrigerant charge.

(See unit head pressure charging chart.)

e. Check compressor current draw in eunps.

f. Check unit for excessive noise, refrigerant tubing

for excessive vibration and for contact with other
parts. Correct as necessary.

g.

Do not leave installation until unit has been

observed through one or two complete cycles. Make

-10-