beautypg.com

Start-up – Carrier 380B User Manual

Page 7

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

INSTALL A BRANCH CIRCUIT DISCONNECT

PER NEC of adequate size to handle unit starting

current. Provide a separate disconnect for outdoor

unit, indoor unit and for each accessory electric

' ■ heater circuit as required. (See Indoor Unit and

Electric Heater Installation, Start-Up and Service

Instructions.) Locate disconnect(s) within sight of

and readily accessible from the unit; per section

440-14 of National Electrical Code (NEC).

ROUTE LINE POWER LEADS INTO UNIT ~

Extend leads from disconnect thru power wiring

hole provided (see Fig. 1) and into unit splice area.

Remove top cover to gain access to unit wiring.

CONNECT GROUND LEAD AND POWER

WIRING — Connect ground lead to a ground lug

in control box for safety. Then connect power

wiring. See Fig. 4. Splice line power leads to yellow

and black pigtails. Use wire nuts and tape at each

connection. Connect unit wiring to copper or

copper-clad aluminum power wiring.

SEE INDOOR UNIT AND ELECTRIC HEATER

INSTALLATION, START-UP AND SERVICE

INSTRUCTIONS for line power wiring details. All

control wiring is shown in this booklet.

CONNECT CONTROL POWER WIRING (24 V)

— Extend wiring thru hole provided (Fig. 1) and

into low-voltage section of unit control ring.

Connect leads to control wiring terminal board as

shown in Fig. 5.

^

Use indoor unit transformer as 24-v supply for

system. At least a 60-va transformer is recom­

mended. Carrier approved indoor units are equipped

with a 60-va transformer. See indoor unit data.

Use Carrier accessory indoor thermostat with

subbase. Table 3.

Accessory Outdoor Thermostat

provides adjust­

able outdoor control of accessory electric heater.

This thermostat makes contact when a drop in out­

door temperature occurs. It energizes a stage of elec­

tric heat when the outdoor temperature setting is

reached, provided the room thermostat is on the

second stage of heating. One outdoor thermostat is

recommended for each stage of electric heat after the

first stage. Set the outdoor thermostat(s) pro­

gressively lower for each stage. Refer to heat load of

building and unit capacity to determine the correct

outdoor thermostat settings.

The accessory supplemental heat relay is required

when 2 outdoor thermostats are used. It is auto­

matically energized by the manually operated

supplemental heat switch in the indoor thermo­

stat subbase. The thermostat locks out compressor

and the relay bypasses the outdoor thermostats for

electric heater operation during heat pump shut­

down. When one outdoor thermostat is used, a

supplemental heat relay is not required. The

supplemental heat switch in the indoor thermostat

subbase bypasses outdoor thermostat, locks out

compressor and activates electric heater.

MOUNT OUTDOOR THERMOSTAT on control

ring, to the left of the low-voltage control connec­

tion. See Fig. 1.

Attach brackets with short sheet metal screws

to avoid contact with coil. Leave capillary tube

coiled in control compartment making sure it is

clear of all electrical connections and sharp metal

edges.

MOUNT SUPPLEMENTAL HEAT RELAY in

convenient location on indoor unit. Attach with

sheet metal screw.

START-UP

The 38QB unit is equipped with a crankcase

heater. It is recommended that heater be energized a

minimum of 24 hours before starting unit. To ener­

gize heater only, turn the thermostat to OFF posi­

tion and close electrical disconnect to heat pump.

Heat Anticipator Settings for Room Thermo­

stat

(HH07AT171) — Set anticipator settings for

room thermostat according to Table 5. These

settings may be changed slightly to provide a greater

degree of comfort for a particular installation.

Table 5 — Thermostat Anticipator Settings

UNIT

38Qa

FIRST-

STAGE

ANTICIPATOR

SETTING

INDOOR

UNIT WITH

ELECTRIC

HEATER

HTR

KW

SECOND-

STAGE

ANTICIPATOR

SETTINGS

( 018

\ - , 024

030
036
042

Fixed

40DQ and

40AQ Fan Coil

with 40AQ Htrs

or 40QB Fan Coii

with 40QB Htrs

50
75

100

25

150
20.0
25 0

50

30 0
34.0

75

To Start Unit

— (Make sure crankcase heater

has been energized for 24 hours.) Adjust the thermo­

stat as follows:

1. Set selector switch at OFF.

2. Turn on main disconnect switch(es) to indoor

and outdoor units.

3. Set fan switch as desired (ON or AUTO.).

4. Set thermostat dial at desired temperature.

5. Set selector switch at HEAT or COOL.

Check system refrigerant charge. See Refrigerant

Charging.

SERVICE