beautypg.com

Table 6 — refrigerant charging methods, Table 5 — service data – Carrier 38EB User Manual

Page 7

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

Table 5 — Service Data

UNIT

R-22 CHG‘

CONDENSER

38EB

(lb)

FAN RPM

015300
018300

3 3

1110

024300

030310

5 3

036310

7 5

042360

6 3

048310

6 1

1075

048350

7 2

060350

9 6

‘Factory refrigerant charge is adequate when evaporator and

condensing unit are the same size and are connected with 25ft
or less of field-supplied tubing of recommended size or Carrier
accessory tubing

When system is not evacuated, subtract the

following amount from total charge.

38EB015 thru 030 — .10 lb (1.6 oz)
38EB036 thru 060 — .20 lb (3.2 oz)

The Dial-a-charge charging cylinder is an accu­

rate device used to recharge system by weight. These
cylinders are available at refrigeration supply firms.

CHARGING CHART METHOD — Use Charging
Chart, Fig. 6, and the following procedure.

1. Operate unit a minimum of 10 minutes before

checking charge.

2. Measure suction pressure by attaching a gage to

suction valve service port.

3. Measure suction line temperature by attaching a

service thermometer to unit suction line near suc­

tion valve. (Insulate thermometer for accurate
readings.)

4. Measure outdoor (condenser inlet) air dry-bulb

temperature with a second thermometer.

5. Refer to Charging Chart (Fig. 6). Find air tem­

perature entering condenser and project hori­
zontally to curve showing suction pressures

(psig at suction valve).

6. From this interseetion, project vertically down­

ward to suction line temperature.

Fig. 6 — 38EB Charging Chart

(AccuRaterT"'' System)

7. If unit has a higher suetion line temperature than

charted temperature, add refrigerant until
charted temperature is reached.

8. If unit has a lower suction line temperature than

charted temperature, bleed refrigerant until
charted temperature is reached.

9. If air temperature entering condenser or pressure

at suction valve changes, charge to new suction
line temperature indicated on chart.

CHARGEMASTER® METHOD — Operate unit
for 10 minutes before using Chargemaster (Carrier

Part No. 38GC680004).

1. Tape Chargemaster feeler bulb to suction line

close to condensing unit. Insulate bulb. Ensure
suction line is clean for good contact with bulb.
(Uninsulated bulb or dirty suction line will seri­

ously affect accuracy of temperature readings.)

2. Connect refrigerant drum to Chargemaster inlet

port keeping drum in position for vapor charging.

Table 6 — Refrigerant Charging Methods

COND UNIT

METHODS OF CHECKING OR

ADJUSTING CHARGE

METHODS FOR COMPLETE

RECHARGING

38EB

System Refrigerant Control

System Refrigerant Control

Non TXV j

TXV

Non TXV

1 TXV

ALL

Chargemaster® |

or 1

Charging Chart 1

Sight

Glass‘

Weight Method

plus

Chargemaster or

Charging Chart

Weight Method

1 plus

1 Sight Glass*

‘Sight glass field supplied and installed In liquid refrigerant line.